Maintenance
Step 6
Press the plate pack together. Position the four tightening bolts
according to the figure.
Tighten the four bolts (1), (2), (3), (4) until the plate pack
measure
A
is 1.10 making sure the frame plate and pressure
plate are parallel when closing.
A
A
3
1
2
4
Step 7
Tighten the four bolts (1), (2), (3), (4) evenly until dimension
A
has been reached.
When a pneumatic tightening device is used, see table below for
maximum torque. Measure dimension
A
during tightening.
Bolt with bearing box
Bolt with washer
Bolt size
Nm
kpm
Nm
kpm
M30
900
90
M39
1300
130
2000
200
M48
2100
210
3300
330
For manual tightening, the tightening torque has to be estimated.
If dimension
A
cannot be reached:
•
Check the number of plates and the dimension
A
.
•
Check that all the nuts and bearing boxes are running freely.
If not, clean and lubricate, or replace.
A
A
3
1
6
5
2
4
Step 8
Mount the remaining locking bolts and check measurement
A
on both sides, top and bottom.
Step 9
Mount protection sheets (if provided).
Step 10
Connect pipes.
Step 11
If the heat exchanger does not seal when measurement A has
been reached, it can be tightened further to
A
minus 1.0%.