CM737-Category 2: System Settings
8.2.2
Parameter
Para
meter
N:o
Factory Default Setting
Optional Setting
Display Description
Display
Description
Category 2 Parameters - System Settings (press PROGRAM to access this category)
Summer heating in
OTC mode
1:SH
0
Summer heating
disabled
1 to 40
Minimum set point for the
heating and the pump will be
held on.
Economy function
2:SL
20
The outside temperature
at which the heating will
switch off
10 to 30
The economy function will be
disabled if the setting for
summer heating is not 0
Economy function
3:Pd
10
Diff between outside and
calculated water supply
temperature
If the calculated water
supply temperature is not
greater than the outside
temperature by this amount
the heating will switch off.
CM737-Category 3: Boiler Settings
8.2.3
Parameter
Para
meter
N:o
Factory Default Setting
Optional Setting
Display
Description
Display
Description
Category 3 parameters
– Boiler settings (press PROGRAM to access this category)
Maximum central
heating set point 2)
1:CH 90
90°C or obtained from
the boiler
40 to 90
40°C to 90°C adjustment in
1°C steps
DHW set point 2)
2:HS 55
55°C or obtained from
the boiler
40 to 80
40°C to 80°C adjustment in
1°C steps
Supply water
temperature 3)
3:St
Actual
temp
Temperature obtained
from the boiler
(between 0°C and
99°C)
N/A
Not applicable
Return water
temperature 3)
4:rt
Actual
temp
Temperature obtained
from the boiler
N/A
Not applicable
DHW temperature
3)
5:Ht
Actual
temp
Temperature obtained
from the boiler
N/A
Not applicable
Outside
temperature 4)
6:Ot
Actual
temp
Between -30°C and
99°C
N/A
Not applicable
Water pressure 3)
7:Pr
Actual
press
Between 0.0 bar and
4.0 bar
N/A
Not applicable
DHW storage
overnight
8:HO 1
DHW storage enabled
after last period of day
0
DHW storage disabled after
last period of day
DHW storage
during HOLIDAY
9:HH 0
DHW storage
disabled during
HOLIDAY
1
DHW storage enabled
during HOLIDAY
Low capacity
control
10:LD
1
Not applicable
0
Not applicable
Содержание AquaMicro
Страница 2: ......
Страница 16: ...Alfa Laval Micro Installation and service instruction 16 Measure sketch 2 9...
Страница 19: ...Alfa Laval Micro Installation and service instruction 19 Picture 12...
Страница 44: ...Alfa Laval Micro Installation and service instruction 44 12 Electrical circuit diagram Micro RTC Picture 35...
Страница 45: ...Alfa Laval Micro Installation and service instruction 45 Micro STC and Micro STC2 Picture 36...
Страница 47: ...Alfa Laval Micro Installation and service instruction 47 Micro RTC 13 3 Picture 39 Micro STC 13 4 Picture 40...
Страница 48: ...Alfa Laval Micro Installation and service instruction 48 Micro STC2 13 5 Picture 41 Micro HTC 13 6 Picture 42...
Страница 60: ...Alfa Laval Micro Installation and service instruction 60 17 Declaration of conformity...