Alfa Laval Micro
Installation and service instruction
29
5
Binding/rebinding the CM721
The binding operation is required if:
Any of the system components (room thermostat or relay box) are replaced.
The relay box has incorrect or no binding data stored e.g. when pre-bound system pack components
have been mismatched.
Pairing the units
1. During the binding procedure keep approximately 1m distance between the room thermostat and the
relay box
.
Picture 22
Reset stored data in the relay box
2. Press and hold the relay box push button for 15 seconds to reset any previously stored data.
After 15 seconds the red LED will change to flashing 0.1sec on/0.9sec off.
NOTE:
After 5 seconds the red LED will start to flash 0.5sec on/0.5sec off, but continue to hold the
button
.
Picture 23
3. Release the push button.
Put Relay Box into Binding mode
4. Press and hold the relay box push button for 5 seconds to enter the binding mode. The Red LED will
start flashing at 0.5sec on/0.5sec off to confirm the binding mode has been entered
Picture 24
Reset stored data in the room unit (if required)
5. Press the
OFF
button on the room thermostat. Then press the
and
butto
ns together along
with the
button. The unit will display InSt and ‘CONTROL BINDING’.
Pairing the units
6. During the binding procedure keep approximately 1m distance between the room thermostat and the
Содержание AquaMicro
Страница 2: ......
Страница 16: ...Alfa Laval Micro Installation and service instruction 16 Measure sketch 2 9...
Страница 19: ...Alfa Laval Micro Installation and service instruction 19 Picture 12...
Страница 44: ...Alfa Laval Micro Installation and service instruction 44 12 Electrical circuit diagram Micro RTC Picture 35...
Страница 45: ...Alfa Laval Micro Installation and service instruction 45 Micro STC and Micro STC2 Picture 36...
Страница 47: ...Alfa Laval Micro Installation and service instruction 47 Micro RTC 13 3 Picture 39 Micro STC 13 4 Picture 40...
Страница 48: ...Alfa Laval Micro Installation and service instruction 48 Micro STC2 13 5 Picture 41 Micro HTC 13 6 Picture 42...
Страница 60: ...Alfa Laval Micro Installation and service instruction 60 17 Declaration of conformity...