Page 4 | Installation Instructions

Testing the Alarm Panel

1a. Test the alarm panel by pressing and holding the test/silence 

 

pushbutton (Fig. 12). If properly installed, all of the LEDs should 

 

illuminate (quick flash) and then after approximately 5-6 seconds, 

 

the buzzer should annunciate (quick pulse). Immediately release 

 

the test/silence pushbutton after the buzzer annunciates a quick 

 

pulse tone to end the test. After the test/silence pushbutton is 

 

released, the alarm panel will auto reset for the next alarm cycle. 

 

Test product weekly to ensure system integrity.

CAUTION:

 Holding the test/silence pushbutton for longer than 5-6 seconds 

along with the buzzer quick pulse tone will change the temperature alarm 

enable or disable setting (approximately 9-10 seconds; total elapsed time). 

See complete user guide for settings information and step 1c below to test 

auxiliary contacts separately.

6. Plug the alarm panel power supply into a standard wall outlet or 

  receptacle (120VAC, 50/60 Hz), and then plug the quick connect 

  of the power supply cord into the incoming power receptacle of 

  the alarm panel. The green power LED should illuminate (solid) 

  when powered (Fig. 11).

(Fig. 13)

(Fig. 12)

(Fig. 11)

Installation of the Alarm Panel 

(continued)

1b. Test the alarm panel by activating the sensor (signaling device) 

 

(Fig. 13). The alarm LED should illuminate (solid), buzzer should 

 

annunciate (solid), and auxiliary contacts should activate for the 

 

zone in which the sensor is connected to. Press the test/silence 

 

pushbutton and the buzzer should silence while the alarm LED 

 

remains on (solid) with activated auxiliary contacts (alarm LED 

 

slow flash) for each zone silenced. After the sensor is deactivated, 

  the alarm panel will auto reset for the next alarm cycle. Test 

 

product weekly to ensure system integrity.

Note: If multiple sensors are used, perform a test for each sensor connected 

to the alarm panel to ensure complete system operation.

Vizzyalarm™ 3-Zone WiFi Alarm Panel - Installation Instructions

5 ft. Max

1c. Test the auxiliary contacts by pressing and holding the test/silence 

  pushbutton immediately followed by pressing and holding the 

 

WiFi/connect pushbutton (Fig. 14). The auxiliary contacts for all 

 

zones connected to the auxiliary terminal block should activate 

 

(alarm  LED  slow  flash).  When  the  WiFi/connect  pushbutton  is 

 

released, the auxiliary contacts for all zones connected to the 

 

auxiliary terminal block should deactivate.

Note: Once the test/silence pushbutton is released, it will exit the auxiliary 

contacts testing mode.

(Fig. 14)

Zone-1; COM and 1A

Building Automation System (BAS)

Another High Water Alarm

Any Monitoring System

Zone-2; COM and 2A

Building Automation System (BAS)

Another High Water Alarm

Any Monitoring System

Zone-3; COM and 3A

Building Automation System (BAS)

Another High Water Alarm

Any Monitoring System