Installation Instructions | Page 3

(Fig. 7; auxiliary contacts)

(Fig. 9)

Auxiliary Contacts:

Zone-1 (1A)

One wire to Terminal COM (common)

One wire to Terminal 1A

Zone-2 (2A)

One wire to Terminal COM (common)

One wire to Terminal 2A

Zone-3 (3A)

One wire to Terminal COM (common)

One wire to Terminal 3A

30VDC, 700mA maximum, Normally Open; Single Pole, Single Throw

Note: The auxiliary dry contacts of the alarm panel are normally open ONLY, 

recommended to use 18 gauge 2-conductor wire. Used for remote monitoring.

Sensor/Signaling Device:

Zone-1 (CH1)

One wire to Terminal COM (common)

One wire to Terminal CH1

Zone-2 (CH2)

One wire to Terminal COM (common)

One wire to Terminal CH2

Zone-3 (CH3)

One wire to Terminal COM (common)

One wire to Terminal CH3

3-10VAC/DC, 10mA minimum, Normally Open or Normally Closed

Note: Use normally open sensors (signaling device) for high level alarm indication 

and normally closed sensors (signaling device) for low level alarm indication.

3. If connecting to an existing alarm security system or building automation system (BAS), use 18 gauge 2-conductor wire 

  to connect the existing product to the auxiliary contact inputs on the terminal block (Fig. 7). See below for wiring 

  information. The zone-1, zone-2, and/or zone-3 auxiliary contacts are activated when the sensor (signaling device) 

  contacts are “closed” during an alarm condition (normally open or normally closed). When connected, run the wire(s) 

  towards the bottom/center of the alarm panel to go through the wiring access hole once the enclosure cover is replaced 

  (Fig. 9 and Fig. 10).

4. Connect the sensor (signaling device) to the sensor/signaling device inputs on the terminal block (Fig. 8). See 

  below for wiring information. The zone-1, zone-2, and/or zone-3 alarms are activated when any “dry” type sensor 

  that “closes” during an alarm condition (normally open or normally closed). When connected, run the wire(s) towards 

  the bottom/center of the alarm panel to go through the wiring access hole once the enclosure cover is replaced 

  (Fig. 9 and Fig. 10).

Note: When installing a sensor or device, always refer to its installation instructions for complete operating information.

CAUTION:

 Route all wires away from sharp objects and internal components when installing wires.

Installation of the Alarm Panel 

(continued)

5. After the wiring is completed and before replacing the enclosure cover, run the wire(s) towards the bottom/center of the 

  alarm panel to go through the wiring access hole once the enclosure cover is replaced (Fig. 9 and Fig. 10).

CAUTION:

 Route all wires away from sharp objects and internal components when installing wires.

(Fig. 10)

Vizzyalarm™ 3-Zone WiFi Alarm Panel - Installation Instructions

(Fig. 8; sensor/signaling device)

(Z1-BAS)

(Z2-BAS)

(Z3-BAS)

(Zone-1)

(Zone-2)

(Zone-3)