background image

Alderon Industries, LLC - Leading Edge Control Products  |  218.483.3034  |  [email protected]  |  [email protected]  |  alderonind.com

Installation Instructions | Page 1

QSG00321_Rev01_Vizzyalarm 3-Zone Indoor Alarm WiFi VZW-01 | November 22, 2021 1:19 PM

Introduction

Before proceeding with the installation or operation of the product, make sure to read all 

instructions thoroughly, as well as complying with all Federal, State and Local Codes, 

Regulations  and  Practices.  The  product  must  be  installed  by  qualified  personnel  familiar 

with all applicable local electrical and mechanical codes. Refer to the National Electrical 

Code (NFPA 70). Failure to properly install and test this product can result in personal injury 

or equipment malfunction. 

Safety Guidelines

Description of Operation

The Vizzyalarm™ 3-Zone WiFi Alarm is an indoor rated alarm panel, powered by a standard 120VAC wall outlet. The green 

power LED will illuminate (solid) when powered. The Vizzyalarm™ is a multipurpose alarm panel that can be used for a 

variety of applications, including but not limited to: septic tanks, sumps, holding tanks, pump chambers, water tanks, flow, 

pressure, condensate, temperature, and any others where a “dry” contact can be connected to the alarm panel. Connect 

and register your wireless device to the Alderon™ cloud based Vizzy.site™ to begin monitoring and receiving text and email 

alerts for system conditions.

The alarm panel is equipped with audible and visual alarm indication, activated by a normally open or normally closed sensor 

wired to the terminals and/or the built-in temperature alarm detection. A variety of sensors can be used such as a float switch, 

pressure switch, or any “dry” type sensor that “closes” during an alarm condition (normally open or normally closed). The included 

3.7VDC LiPo rechargeable battery (not installed) provides battery backup during power outages. Use the auxiliary contacts 

to connect to building automation systems (BAS) and phone dialers. Multiple sensors (signaling device) can be connected for 

expanded monitoring.

An alarm condition occurs when the sensor (signaling device) contact for zone-1, zone-2, and/or zone-3 is activated, during 

which the red alarm LED(s) will illuminate (solid), buzzer will annunciate (solid), and the auxiliary contacts will activate. The alarm 

condition will stay on until the sensor for the zone(s) activated are deactivated. If the test/silence pushbutton is pressed 

during an alarm condition, it will silence the buzzer while the alarm LED remains on (solid) with activated auxiliary contacts 

(alarm LED slow flash) for each zone silenced. The silence condition will reset when the sensor for zone-1, zone-2, and/or 

zone-3 deactivates and the alarm panel will auto reset for the next alarm cycle.

Note: If zone-1 is in an alarm condition and the buzzer is silenced, and then zone-2 and/or zone-3 goes into an alarm condition, the buzzer will reactivate 

until the test/silence pushbutton is pressed to acknowledge that a new alarm condition has occurred.

1.  DISCONNECT ALL ELECTRICAL SERVICE BEFORE WORKING ON OR HANDLING THE PRODUCT.
2.  DO NOT USE WITH FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, KEROSENE,  ETC. 

  DO NOT USE IN EXPLOSIVE ATMOSPHERES.
3.  ALARM PANEL MUST BE MOUNTED INDOORS. FOR OUTDOOR APPLICATIONS, CONSULT FACTORY.

Specifications

Primary Power

120VAC, 50/60 Hz

Circuit Board Primary Power

11.1VDC, 500mA maximum

Circuit Board Secondary Power

3.7VDC, 1800mAh (battery backup)

LiPo battery, model LP683857

Field Connection Sensor

3-10VAC/DC, 10mA minimum

(signaling device)

Auxiliary Contacts

30VDC, 700mA maximum

Normally Open; Single Pole, Single Throw

Enclosure

Thermoplastic

5 x 4 x 1.3 (inches)

Type 1, Indoor

Removable cover

Certifications

CSA (US and Canada)

FCC Part 15 (US and Canada)

Three-Year Limited Warranty

LEDs

Green (power), Red (alarms),

and Blue (Vizzy/WiFi)

Buzzer

85 dB @ 10-feet

Wall-Mounted Power Supply

120VAC, 50/60 Hz (input)

11.1VDC, 500mA maximum (output)

(6-foot cord)

Temperature Alarm 

(detection range)

-40°C/-40°F to 46°C/115°F

Operation, Maintenance, and Installation Manual

Vizzyalarm

 3-Zone Alarm

WiFi, Model: VZW-01 | Rated Type 1 (Indoor), Alarm Panel