ALCO AL-85851 Скачать руководство пользователя страница 4

Page 4 

and reliability as if the access system experiences a fault, the XMS still allows safe egress.  If the 
access system is not monitoring the door, connection to the REX input is not required.  In that 
case, make all other connections as shown in Figure 5 except the REX input. 

FIG. 5:  WIRING WITH AN ACCESS CONTROL SYSTEM 

12-28 VDC

POWER

 SUPPLY

+

-

MAGNETIC LOCK

+

-

+

-

XMS

REX

INPUT

C

NC

ACCESS SYSTEM LOCK CONTROL RELAY

USE 1/2 SECOND TIME

SETTING WITH ACTIVE REX

(SEE SECTION 5)

IN+ D  VICE

C1 NC1 NO1

FIG. 6:  WIRING WITH “GENERIC” PUSH BUTTON AND TIMER 

12-28 VDC

POWER

 SUPPLY

+

-

MAGNETIC LOCK

+

-

+

-

XMS

REX

INPUT

C

NC

ACCESS SYSTEM LOCK

CONTROL RELAY

TM-8L

TIMEMATE

C

NC

YEL

RED

GRN

WHT

BLK

PUSH BUTTON

NO

USE 1/2 SECOND TIME

SETTING WITH ACTIVE REX

(SEE SECTION 5)

IN+ D  VICE

C1 NC1 NO1

3.5  “ACCESS CONTROLLED EGRESS DOOR” 
In some jurisdictions, the combination of a magnetic lock, access control system and exit 
detector such as the 

AL-85851

 can be considered an “access controlled egress door”.  The 

applicable section of the Life Safety Code calls for a redundant means of exit in the event of a 
problem with the detector.  This is typically a push button located 40-48” above the floor and 
within five ft. of the door.  Pushing the button will directly release power to the magnetic lock 
and the lock shall remain released for 30 seconds.  This can be accomplished with any of 

the

 

push buttons and the model TM-8L timer.  Figure 6 shows proper wiring. 

ALCO

 also manufactures a line of push buttons with integrated timers (

AL-85852

).  

These are easier to use with the 

AL-85851

 to satisfy the code requirements for access 

controlled egress doors.  Figure 7 shows wiring with the integrated push button/timers. 

[email protected]   

|

    800.323.4282  

|

   www.alcosales.com

Содержание AL-85851

Страница 1: ...e make sure you are complying with local building codes Contact your building and or fire prevention department 2 PHYSICAL INSTALLATION 2 1 PLACEMENT OF THE UNIT The AL 85851 is intended for indoor us...

Страница 2: ...cover The appearance of the interior is shown in Figure 2 Note that the interior electronics is mounted on a rotating barrel which is locked by the Barrel Locking Screw shown in Figure 2 Loosen this...

Страница 3: ...TO ALARM PANEL DOOR SWITCH TO ALARM PANEL ALARM SIGNAL WHICH IS CLOSED WHEN DOOR IS CLOSED OPENS TO ALARM ALARM SIGNAL WHICH IS OPEN WHEN DOOR IS CLOSED CLOSES TO ALARM IN DEVICE C1 NC1 NO1 IN DEVICE...

Страница 4: ...NO1 3 5 ACCESS CONTROLLED EGRESS DOOR In some jurisdictions the combination of a magnetic lock access control system and exit detector such as the AL 85851 can be considered an access controlled egres...

Страница 5: ...ou need to understand how the unit s control outputs operate in a detection event In the rest condition green LED on no detection the lock control transistor is conducting and the REX relay is deenerg...

Страница 6: ...control relay can be altered by changing jumper settings see Section 5 but the REX relay always operates 50 milliseconds before and one second after the lock control transistor Figure 8 shows the tim...

Страница 7: ...entry security Before doing this set the time set jumper to the 1 2 second position shown in the drawing to the right As you are adjusting the pattern you will make many quick tests of the unit and t...

Страница 8: ...iming screw settings you must also finalize the degree of barrel assembly rotation You don t want the unit seeing the surface of the door itself as this can lead to false detection so in the common ca...

Отзывы: