FIG. 3:  WIRING WITH MAGNETIC LOCK ONLY 

12-28 VDC

POWER

 SUPPLY

+

-

MAGNETIC LOCK

+

-

+

-

AL-85851

MATCH POWER

 SUPPLY VOLTAGE TO

MAGNETIC LOCK

VOLTAGE

IN+ D  VICE

C1 NC1 NO1

Note that how positive power to the lock connects through the terminal block “IN+” and 
“DEVICE”.  These two terminals constitute an internal field effect transistor which does the 
actual  switching.    If  power  to  the  XMS  was  somehow  interrupted,  the  field  effect  transistor 
would  automatically  open  (releasing  power  to  the  lock).    This  makes  the 

AL-85851

  “fail 

safe”.    Note:  never  use  the  REX  relay  contacts  to  switch  the  magnetic  lock.    These 
contacts  only  have  enough  capacity  for  signaling;  they  cannot  reliably  switch  magnetic  lock 
current. 

If you need to integrate a controlled entry unit such as a digital keypad, use a set of NC 
contacts from the entry unit to break the wire between “DEVICE” and magnetic lock “+” to allow 
the entry unit to release the lock. 

3.3  SHUNTING AN ALARM POINT 
This technique is for installations where the door is connected to an alarm system and that if 
the  door  opens  without  the 

AL-85851

  having  been  activated,  an  alarm  signal  should  result.  

When the 

AL-85851

 is employed to open the door, the alarm signal should be shunted. 

FIG 4:  WIRING TO SHUNT ALARM SYSTEM ON DOOR 

DOOR

SWITCH

TO ALARM PANEL

DOOR

SWITCH

TO ALARM PANEL

ALARM SIGNAL WHICH IS
CLOSED WHEN DOOR IS CLOSED:
OPENS TO ALARM

ALARM SIGNAL WHICH IS
OPEN WHEN DOOR IS CLOSED:
CLOSES TO ALARM

IN+ DEVICE

C1 NC1 NO1

IN+ DEVICE

C1 NC1 NO1

The alarm system will be connected to a door switch or other detector at the door via two wires. 
You will need to determine if this “loop” is closed when the door is closed and opens when the 
door opens or is open when the door is closed and closes when the door opens.  Correct wiring 
to shunt the alarm is shown in Figure 4 for either instance.  You utilize the “REX” relay contacts 
for this shunting while the lock control relay contacts continue to release the magnetic lock. 

3.4  INTEGRATION WITH ACCESS CONTROL SYSTEM 
An access control system permits entry (generally from a card reader) and will also often act as 
an alarm system if a door is forced.  To integrate with the 

AL-85851

 and a magnetic lock, the 

access  system  should  have  a  two-terminal  REX  (request  to  exit)  input.    When  this  input  is 
closed,  the  access  system  will  operate  its  lock  control  relay  to  release  the  lock  and  will  not 
create an alarm signal as it will consider the exit event a “legal” one.  Wiring is shown in Figure 
5.  Note that with this wiring method, the lock control terminals of the 

AL-85851

 directly break 

power  to  the  magnetic  lock  as  do  the  access  system  contacts.    This  is  called  “double  break” 
wiring.  It enhances safety 

[email protected]   

|

    800.323.4282  

|

   www.alcosales.com

Содержание AL-85851

Страница 1: ...e make sure you are complying with local building codes Contact your building and or fire prevention department 2 PHYSICAL INSTALLATION 2 1 PLACEMENT OF THE UNIT The AL 85851 is intended for indoor us...

Страница 2: ...cover The appearance of the interior is shown in Figure 2 Note that the interior electronics is mounted on a rotating barrel which is locked by the Barrel Locking Screw shown in Figure 2 Loosen this...

Страница 3: ...TO ALARM PANEL DOOR SWITCH TO ALARM PANEL ALARM SIGNAL WHICH IS CLOSED WHEN DOOR IS CLOSED OPENS TO ALARM ALARM SIGNAL WHICH IS OPEN WHEN DOOR IS CLOSED CLOSES TO ALARM IN DEVICE C1 NC1 NO1 IN DEVICE...

Страница 4: ...NO1 3 5 ACCESS CONTROLLED EGRESS DOOR In some jurisdictions the combination of a magnetic lock access control system and exit detector such as the AL 85851 can be considered an access controlled egres...

Страница 5: ...ou need to understand how the unit s control outputs operate in a detection event In the rest condition green LED on no detection the lock control transistor is conducting and the REX relay is deenerg...

Страница 6: ...control relay can be altered by changing jumper settings see Section 5 but the REX relay always operates 50 milliseconds before and one second after the lock control transistor Figure 8 shows the tim...

Страница 7: ...entry security Before doing this set the time set jumper to the 1 2 second position shown in the drawing to the right As you are adjusting the pattern you will make many quick tests of the unit and t...

Страница 8: ...iming screw settings you must also finalize the degree of barrel assembly rotation You don t want the unit seeing the surface of the door itself as this can lead to false detection so in the common ca...

Отзывы: