unit is simply centrally positioned above the door with the pattern covering the door (setting the 
pattern is addressed later in this manual). 

For  security applications, you will set your position to defend against someone activating the 
detector from the outside.  This can be done by inserting a heated object under the door.  To 
deal with this threat, the unit is positioned above and outside of the door hinges with the pattern 
adjusted so that it sweeps across the door but does not detect the bottom of the door.  If the 
door includes an exit bar, the pattern must be broad as a person’s approach to the door is 
variable.  If it includes a door knob or lever handle, the pattern can be adjusted more 
narrowly
.  A final option for security applications is to position the unit at the side of the door 
so that it sees across the door.  This can be used for doors at the end of corridors.  You would 
not want to employ this approach for non corridor doors as the door would be released by 
someone walking near it (maximum detection range is 20-25 ft.)  Side of door mounting has the 
disadvantage of greater exposure to vandalism but defends against objects being inserted under 
the door and provides excellent coverage along the full width of the door.  Note that for the end-
of-corridor application, the unit can be positioned on the same wall plane as the door or on a 
wall which is next to the door and perpendicular to it.  You have the choice because the pattern 
can be adjusted a full 90 degrees with respect to the sensor’s mounting plane. 

2.2  FIXING THE UNIT TO THE WALL 
First, locate the screw on the end of the unit and loosen it.  This permits you to remove the 
cover.  The appearance of the interior is shown in Figure 2.  Note that the interior electronics is 
mounted on a rotating barrel which is locked by the “Barrel Locking Screw” shown in Figure 2. 
Loosen this screw and rotate the barrel fully upward so that you can remove it.  This leaves you 
with the back piece and you will see two slotted holes for physical mounting and a choice of two 
wire entry points (also shown on Figure 2).  Most installers prefer to pull the cable through the 
wall first and then mount the unit.  If you’re not sure of your wire count for the cable, consult 
the next section at this time but completion of physical installation consists only of screwing the 
back piece to the wall and pulling the cable through one of the wire entries.  Then you will 
replace the barrel assembly and attach the wires to the screw terminals. 

FIG. 2:  

AL-85851

 OVERVIEW 

IC

A B

LED FAST

IN+ DEVICE

C1 NC1 NO1

BARREL LOCKING

 SCREW

+

-

12-28 VDC

POWER

LOCK CONTROL

REX RELAY

WIRE

ENTRY
HOLES

AIMING

SCREWS

SENSITIVITY

JUMPER

LED LOGIC

JUMPER

TIME SET

JUMPER

BI-COLOR

LED

3.

 

WIRING

3.1  INPUT POWER
To power the unit, filtered and regulated DC voltage between 12 and 28 volts should be applied 
to the power input terminals (see Figure 2).  This connection should be permanently made to 
the power supply rather than switched through some other device.  The 

AL-85851

 should 

receive constant power.  Make sure you observe correct polarity with this connection.  If you 
reverse the input power polarity, the unit will not be damaged but will appear to be dead.  
Power consumption for the XMS is approximately 20 mA

3.2  WIRING WITH MAGNETIC LOCK ONLY 
This is the simplest application which releases the magnetic lock from the inside for free egress 
but is not concerned with shunting any alarm point at the door.  It is shown in Figure 3. 

INPUT

[email protected]   

|

    800.323.4282  

|

   www.alcosales.com

Содержание AL-85851

Страница 1: ...e make sure you are complying with local building codes Contact your building and or fire prevention department 2 PHYSICAL INSTALLATION 2 1 PLACEMENT OF THE UNIT The AL 85851 is intended for indoor us...

Страница 2: ...cover The appearance of the interior is shown in Figure 2 Note that the interior electronics is mounted on a rotating barrel which is locked by the Barrel Locking Screw shown in Figure 2 Loosen this...

Страница 3: ...TO ALARM PANEL DOOR SWITCH TO ALARM PANEL ALARM SIGNAL WHICH IS CLOSED WHEN DOOR IS CLOSED OPENS TO ALARM ALARM SIGNAL WHICH IS OPEN WHEN DOOR IS CLOSED CLOSES TO ALARM IN DEVICE C1 NC1 NO1 IN DEVICE...

Страница 4: ...NO1 3 5 ACCESS CONTROLLED EGRESS DOOR In some jurisdictions the combination of a magnetic lock access control system and exit detector such as the AL 85851 can be considered an access controlled egres...

Страница 5: ...ou need to understand how the unit s control outputs operate in a detection event In the rest condition green LED on no detection the lock control transistor is conducting and the REX relay is deenerg...

Страница 6: ...control relay can be altered by changing jumper settings see Section 5 but the REX relay always operates 50 milliseconds before and one second after the lock control transistor Figure 8 shows the tim...

Страница 7: ...entry security Before doing this set the time set jumper to the 1 2 second position shown in the drawing to the right As you are adjusting the pattern you will make many quick tests of the unit and t...

Страница 8: ...iming screw settings you must also finalize the degree of barrel assembly rotation You don t want the unit seeing the surface of the door itself as this can lead to false detection so in the common ca...

Отзывы: