Installing Power Modules
7450 ESS-7
Page 79
Connecting the AC Power Cord
Figure 25: AC Power Cord Example
Follow these steps to connect the AC power cord.
Step 1
Locate your AC power cord(s). Verify that the cords meet your regional requirements. Do
not use cords that do not meet these standards.
Step 2
Plug the cords into the receptacle on each AC PEM.
Step 3
Engage the cord retainer by engaging the retainer bracket toward the power cord and snap
the bracket in place (see
). The power cord retainer prevents the power cord
from being accidentally pulled out.
Step 4
Plug the other end of the power cord into the AC power source receptacle.
Step 5
Turn the circuit breaker on each unit to the
ON
position ( | ).
Step 6
Installing the SF/CPM on page 81
Table 27: AC Power Cord Specifications
Component
Specification
Wire type
14 AWG 3 SJT
Conductors
North American
NOM O.D.
.360-.395
Rating
15A/250V
Supply end
NEMA-L6-15P
Equipment end
IEC-60320-C19