Installing DC PEMs
Page 68
7450 ESS-7
DC-Input Power Wiring
Preparing the Power Cable
Connect the VDC and RTN studs on the DC terminal block with power cables terminated with lugs
such as a Panduit LCC6-10A-L copper, standard barrel, 2-hole lug with two .200-inch (
.508
cm)
diameter holes on a .625-inch (1.6 cm) spacing (
The other non-terminated end of the power cables must be prepared according to your local safety
codes. The length of the power cable depends on the location of the router and proximity to the
power source.
Figure 17: DC Terminal Block Lug
Figure 18: Preparing the DC Cable
Warning:
• Ensure that all power is OFF from the DC circuit. Locate the circuit breaker on the panel board
that services the DC circuit. Flip the circuit breaker to the
OFF
( O ) position.
• When wiring the unit, the ground connection must always be made first and disconnected last.
• The proper wiring sequence is ground/negative to ground/negative and positive/return to
positive/return.
• Use a #6 AWG for the -48 and RTN power connections.
0.750"
0.250
2 Holes
All measurements in inches.
SR12030
.200
.625
1
2
SR10030
Содержание 7450 ESS-7
Страница 1: ...7450 ESS 7 INSTALLATION GUIDE February 2008 Document Part Number 93 0048 07 01 93 0048 07 01...
Страница 6: ...Page 6 7450 ESS 7 Table of Contents...
Страница 14: ...Preface Page 14 7450 ESS 7...
Страница 28: ...Chassis Features Page 28 7450 ESS 7 Figure 6 7450 ESS 7 DC Power Entry Module SR70022...
Страница 36: ...7450 ESS 7 System Installation Process Page 36 7450 ESS 7...
Страница 108: ...Installing MDAs Page 108 7450 ESS 7...
Страница 116: ...LEDs and Optics Page 116 7450 ESS 7...
Страница 158: ...Pinout Assignments Page 158 7450 ESS 7...