Installing the 7450 ESS-7
7450 ESS-7
Page 57
M
AKING
THE
C
HASSIS
G
ROUND
C
ONNECTION
Prepare your ground cable with a standard barrel, 2-hole lug with two .25-inch (.635 cm) diameter
holes on a 5/8-inch (1.5875 cm) hole spacing, such as a Panduit LCCF6-14A-L. Grounding cables
are not provided. To make sure that the equipment is connected to earth ground, follow the
instructions to prepare the ground wire. The length of the grounding wire depends on the location
of the router and proximity to the proper grounding facilities.
P
REPARING
THE
G
ROUND
W
IRE
Figure 14: Preparing the Ground Wire
Danger:
Only trained and qualified personnel should install or replace this equipment.
Notes:
When wiring any Alcatel-Lucent 7450 system, the ground connection must always be
made first and disconnected last.
1
2
SR10030
Table 19: Preparing the Ground Wire
Key
Description
1
Copper wire (#6 AWG)
2
Insulation stripped 1 5/16"
Содержание 7450 ESS-7
Страница 1: ...7450 ESS 7 INSTALLATION GUIDE February 2008 Document Part Number 93 0048 07 01 93 0048 07 01...
Страница 6: ...Page 6 7450 ESS 7 Table of Contents...
Страница 14: ...Preface Page 14 7450 ESS 7...
Страница 28: ...Chassis Features Page 28 7450 ESS 7 Figure 6 7450 ESS 7 DC Power Entry Module SR70022...
Страница 36: ...7450 ESS 7 System Installation Process Page 36 7450 ESS 7...
Страница 108: ...Installing MDAs Page 108 7450 ESS 7...
Страница 116: ...LEDs and Optics Page 116 7450 ESS 7...
Страница 158: ...Pinout Assignments Page 158 7450 ESS 7...