4200–063
R4.3
18
Parameters
/
Features
Number
of
cell
channels:
Up
to
six
strings
of
40
12
‐
volt
jars.
Measurement
Range
/
Tolerance
Cell
voltage:
0
to
20V,
0.15%
of
reading
±4mV
Cell
resistance:
0
to
32,000µ
,
5%
of
reading
±1
String
voltage:
0
to
600.0V,
0.2%
of
reading
±0.5V
Intertier
resistance:
0
to
5m
,
5%
of
reading
5
.
Temperature:
0
C
to
80
C
(32
F
to
176
F),
1
C.
Discharge
current:
0
to
4000A
5%
of
full
scale
(using
CT)
Float
current:
0
to
5000mA
±50mA.
*Optional
current
transducer
required.
*Transducer
accuracy
affects
overall
current
reading
accuracy.
Communication
Protocol:
MODBUS,
and
SNMP.
Local
port,
USB
connector–front
panel
Local
port,
RS–232
DB–9
connector
–rear
panel
LAN
port,
RJ–45–Optional;
rear
panel
RJ–11
TELCO
line,
internal
14.4Kbs
modem–rear
panel
(optional)
Fiber
optic
ports:
two
for
system
communications
Data
Storage
SRAM
(8
MB)
nonvolatile
memory
for
all
configuration
settings
and
data
Flash
memory
for
firmware
upgrades
Control
Switches
Power
on/off:
Main
DCM
power
switch
on
rear
panel
of
BDS
Controller
module.
Rocker
switch.
Alarm
Reset
switch
on
front
panel
of
BDS
Controller
module.
Momentary
push
button.
DCM
and
String
ID:
DIP
switch
on
rear
panel
for
setting
string
identification.
Operating
Environment
Temperature
range:
5
C
to
40
C
(41
F
to
104
F).
Humidity
range:
0%
to
80%
RH
(non
condensing)
at
5
C
to
31
C.
0%
to
50%
RH
(non
condensing)
at
32
C
to
40
C.
Indoor
use
only.
Installation
category
II.
Pollution
degree
2.
Altitude
0
to
2000
meters
above
sea
level.
Dimensions
19"W
x
16.2"D
x
7.8"H
34
lbs.