Specifications
4200
‐
063
R4.3
17
4.
Specifications
4.1
BDS–40 Base Unit
Power
115/230VAC
10%
50/60Hz
2
Amps
maximum
for
a
maximum
configuration
of
one
Base
unit
and
five
plus
units
with
a
total
of
40
jars.
Fuses
One
1A
MDL
for
each
string
On
PC
board
Not
user
replaceable
One
2A
SB,
MDL
or
equivalent
AC
power
block
rear
panel
Inputs
24VAC.
40
cell
voltage
channels.
Remote
alarm
reset.
User
‐
supplied
12V
signal.
(Current
50mA
maximum.)
Momentarily
applying
voltage
initiates
the
reset
action.
Ten
intertier
resistance
channels
for
cabinet
configurations.
Eight
interiors
maximum
for
Open
Rack
Configurations:
0
‐
20
jars
=
4
intertiers
21
‐
30
jars
=
6
intertiers
31
‐
40
jars
=
8
intertiers
Two
temperature
channels.*
One
discharge
current
channel.*
One
float
current
channel.*
*Optional
temperature
and
current
transducers
are
required.
Outputs
24VAC
power
for
up
to
five
plus
units.
Alarm
contacts:
Two
Form
C,
2A
at
30VDC.
One
for
critical
alarm,
and
one
for
maintenance
alarm.
LEDs
(one
each):
Green
(G)
DCM
TX
transmit
Green
(G)
DCM
RX
receive
Green
(G)
status
Green
(G)
com
port
Yellow
(Y)
critical
alarm
Yellow
(Y)
maintenance
alarm
Green
(G)
resistance
test
Green
(G)
DCM
status
Green
(G)
TX
transmit
Green
(G)
RX
receive
Red
(R)
service
Содержание BDS-40