background image

 

 

Copyright © 2012 Alarm.com

 

|

 

www.alarm.com 

v2.0

 

 

NetworX CDMA Module

 

|

 

Installation Guide 

 

Locate the module near an outside wall, preferably on an upper level. 

 

Leave 12 to 18 in. (30 to 45 cm) of open space above the module for the 
antenna. 

 

For homes or businesses located in canyons or with hills nearby, it is 
necessary to place the antenna higher in the building. 

Mounting                                                                                 

 

To mount the module, do the following: 

1)

 

Press down on the top of the enclosure cover (Figure 2) and set it aside. 

Figure 2: Enclosure Cover 

 

2)

 

Snap the antenna onto the antenna connector (See

 

Figure 3). 

To 

connect the antenna, place one of your thumbs or fingers behind the 
antenna connector. 

With your other hand, press the end of the micro-

miniature coaxial connector into the antenna connector until you 
head a slight click.

 

Figure 3: Antenna connector and mounting holes 

 

3)

 

To avoid placing unnecessary strain on the antenna connector, which 
can damage the module, use either of the following orientations 
shown in 

Figure 4.

 

 

Figure 4: Antenna wire orientation 

 

 
 

4)

 

Place the module back plate on the wall at the desired mounting location, 
check for level, and mark the three mounting holes and the wire access 
area (Figure 3). Be sure to leave at least 12 to 18 in. (30 to 45 cm) above 
the back plate for the antenna. 

5)

 

Set the back plate aside and drill holes at the mounting and wire access 
area locations. 

6)

 

Use wall anchors where studs are not present and secure the back plate to 

the wall with the enclosed screws. 

CAUTION:

 You must be free of static electricity before handling electronic 

components. Touch a grounded metal surface before touching the board. 

Wiring                                                                                       

To wire the module to the panel, do the following: 

1)

 

Remove panel AC Power and disconnect the backup battery. 

2)

 

Wire the module to the panel POS, COM and DATA terminals (as shown in 

Figure 5

). 

Figure 5: Wiring Terminals 

 

Power Up                                                                                 

To power up the module and panel and start communication between them, 
do the following: 

1)

 

Verify that all wiring between the panel and module is correct. 

2)

 

Connect the backup battery and restore AC power to the panel. 

Note:

 

Whenever any module is added or changed, you must remove panel 

power and reapply it for the panel and module to communicate 
successfully. 

 

3)

 

Verify that radio status LED 1 is not flashing any errors (see 

Radio Status 

LEDs

 on page 3). Also, verify that LED 4 is flashing a signal level of two or 

higher. Otherwise, relocate the module. If LED 1 and LED 4 are not 
flashing, and LED 2 and LED 3 are flashing together, the module is in 
PowerSave mode and the battery needs to be charged. 

4)

 

Perform a manual phone test by pressing 

*44

 while the system is 

disarmed 

(Make sure that panel’s Location 37, Segment 2, Bit 7 is set).

 

Note:

 

if Location 37, Segment 2, Bit 6 is set, performing the phone test 

will trigger the local siren. To avoid triggering the siren when 
performing the phone test, make sure Bit 6 is OFF. 

 

The panel will not show any indication that the phone test signal has been 
sent. You can check the radio status LEDs L3 and L4: L4 should be blinking on 
for 2 seconds and off for 2 seconds. L3 will blink once briefly as soon as you 
press *44. If the account is reporting to a Central Station, wait for a minute 
and check with the Central Station to see if the phone test signal was 
received correctly. The phone test is also used by Alarm.com to set the 
module's parameters the first time the module is powered up. It ensures that 
Alarm.com will receive the sensors list and any other information required 
for proper signaling. 
 

Enrolling the Module                                                           

 

The NetworX control panels have the ability to automatically find and store 
in memory the presence of all keypads, zone expanders, wireless receivers, 
output modules, and any other device on the keypad bus. This allows these 
devices to be supervised by the control panel. To enroll the devices, enter 
Program Mode using the procedure outlined in the control panel installation 
manual. When you exit Program Mode, the control panel will automatically 
enroll the devices. The enrolling process takes about 12 seconds, during 
which time the “Service” LED will illuminate. User codes will not be accepted 
during the enrolling process. Once a module is enrolled, if it is not detected 
by the control, the “Service” LED will illuminate. When initially powering up, 
the control panel automatically performs the device enrollment process. 

 

 
 

Press down 
here  

POS     COM    DATA 

 

Gateway 

 

Panel 

 

KP POS      KP COM      KP DATA 

 

Mounting Hole  

Mounting Hole  

Mounting Hole  

Antenna Connector 

 

Loop the wire and feed 
it back through top 

Feed the wire through 
the bottom of the case 

Содержание NX-208E

Страница 1: ...ific error See Table 5 for errors and common fixes L2 Panel Communication and Z Wave status messages Flashes every time the module communicates with the panel and flashes in patterns to indicate Z Wave status L3 CDMA Communication Flashes every time the CDMA signal level is checked and when packets are exchanged with Alarm com L4 CDMA Signal Level Flashes 0 to 5 times to indicate signal strength o...

Страница 2: ... module to communicate successfully 3 Verify that radio status LED 1 is not flashing any errors see Radio Status LEDs on page 3 Also verify that LED 4 is flashing a signal level of two or higher Otherwise relocate the module If LED 1 and LED 4 are not flashing and LED 2 and LED 3 are flashing together the module is in PowerSave mode and the battery needs to be charged 4 Perform a manual phone test...

Страница 3: ...n indication that the module is fixing an unusual condition regarding communication with the CDMA network 7 There are bit sets in Location 21 that prevent Alarm com from getting the sensor list from the panel In Location 21 segment 1 if bits 5 and 6 are set the module can not retrieve the sensor list Note that bit 7 will prevent location 21 from being displayed at the keypad Bits 5 6 and 7 can onl...

Страница 4: ...Name Programming Mode Then enter 192 for the module serial number or 190 for the reports list By default the keypad shows Zone 190 or Zone 192 To tell the CDMA module to show its information in place of these zone names add a space in front of the zone names by pressing the Stay button followed by star button and pound button to validate the entry When you are done with all 3 zones press Exit to l...

Страница 5: ...ferred login name for the customer Alarm com Module Serial Number At the end of the account creation process you will be able to print a Welcome Letter for the customer that has their login information and temporary password for the Alarm com website FCC Compliance Changes or modifications not expressly approved by Alarm com can void the user s authority to operate the equipment This equipment has...

Отзывы: