Alarko Carrier AIROStar 39SQ Скачать руководство пользователя страница 24

24

6 - MAINTENANCE AND OPERATING INSTRUCTIONS

6.1 - General

The smooth inside and outside finish of the panels makes 
maintenance very simple.

For dry sections: twice a year thoroughly check the inside 
and outside of the AHU casing. For maintenance of wet 
sections (coolers) please refer to the air handling section 
concerned.

All work must be carried out by sufficiently trained 
personnel.

All applicable personal safety devices must be used to 
ensure safe working conditions. Safety gloves,glasses and 
shoes must be worn for all maintenance operations. A 
respiratory protection mask must be worn when changing 
the filters. 

No holes must be drilled into the AHU, to prevent leakage 
from the AHU, cooling coils and heating coils and damage 
to the wiring.

6.2 - Casing panels

6.2.1 - Inside installation

a)  Internal inspection of the casing of double-skin panels 

and of all dry parts.

 

Remove contamination with water and a mild 
household soap solution. Where damage of the paint 
finish has occurred, if necessary remove rust and 
touch up with good quality anti-corrosive primer and 
paint. The outside air intake sections can show signs 
of corrosion as they contain wet parts and are affected 
by mist, rain and air pollutants.

b)  Outside inspection of the coating. 

 

If damage to the paint treatment has occurred, remove 
the rust (if necessary), and touch up with good quality 
anti-corrosive primer and paint.

 

6.2.2 - Outside installation

Check the sealed joints of AHUs installed outside and if 
required seal again with a UV-resistant and paintable kit. 
Repair damage as described for inside installation. Check 
the roof for leaks and if necessary, repair them.

6.3 - Doors and access covers

Check locks and hinges of all doors and access covers. 
Check that the bolt of the internal roller is still correctly 
tightened.

6.4 - Flexible connections

Check the flexible connections for damage. 

6.5 - Earthing

Ensure that the unit is earthed and installed in the correct 
manner.

6.6 - Dampers

Lubrication of the dampers is not required. Remove excess 
contamination by cleaning with compressed air and 
possible cleaning with water and a mild household soap 
solution. Ensure that the damper blades run free in the 
casing.

6.7 - Outside air intake

The outdoor air intake is contaminated by pollution taken in 
with the air. The maintenance interval must be observed, as 
irreparable damage of the panels might otherwise occur. 
Clean the outdoor air intake well and repair damage as 
described in point 6.2.1. Ensure that no moisture (droplets) 
is taken in. If there is still moisture, ensure that this is 
corrected by changing the outdoor air intake duct.

6.8 - Filters

The filters must be inspected once a month for excess 
pollution, pressure loss, damage and seating of the slide-in 
filters or built-in frames. With slide-in filters ensure that the 
filters have been correctly positioned and have been 
pushed well against each other from below. When replacing 
built-in filters you must ensure that the filter has been pushed 
well against the sealant and that the clips have been 
correctly installed. Filters must be replaced at the required 
intervals. The timing of the replacement depends on the 
type of filter, quality and the degree of contamination of the 
air. The pressure loss across the contaminated filter can be 
measured with a pressure differential gauge.

A respiratory protection mask, type P2 and safety gloves 
must be worn when changing the filters. Open flames are 
forbidden while changing the filters to prevent setting fire to 
the filter medium. This is indicated by a sticker on the door 
or hatch.

6.9 - Heaters

6.9.1 - Hot-water coil

Check the air intake once a year for contamination, and if 
necessary clean with compressed air against the direction 
of the air flow or clean the air intake with a vacuum cleaner.

Checking the heaters: Check the operation of the frost 
protection thermostat and check the correct control 
sequence when the themostat trips.

For coils filled with glycol please check if the mixture has 
the correct glycol concentration (by weight).

Содержание Carrier AIROStar 39SQ

Страница 1: ...39SQ 39SQR 39SQP Airostar Air Handling Units Installation operation and maintenance instructions...

Страница 2: ...an 16 4 11 Silencers 19 4 12 Lighting 19 4 13 Control panel 20 4 14 Installation of external sensors included 21 4 15 Sensor Replecament 22 5 MAINTENANCE CHECKLIST 23 5 1 Checklist of check points and...

Страница 3: ...guidelines of the Pressure Equipment Directive PED Do not walk on the roof panels of units installed inside or outside Technical staff who is responsible for startup and maintanence has to take occupa...

Страница 4: ...tted to carry out work on these components Do not work on electrical components including control panels switches VFD untill you are sure ALL POWER IS OFF and no residual voltage can leak from capacit...

Страница 5: ...ple in the immediate vicinity of the unit are endangered Carrier does not accept any responsibility if these instructions are not observed Transport and lifting must be carried out by qualified person...

Страница 6: ...mended for direct drive fans 2 6 Warranty The units will 2 years warranty after invoice date if startup storage and maintenance are made according to this manuel 2 7 Placement The unit have to be plac...

Страница 7: ...t recovery wheel I Recirculation damper J Supply air fan K Extract air filter L Electric reheater hot water M Cooling coil with changeover N Supply air damper O Extract air damper Legend 1 Actuator ou...

Страница 8: ...ypass damper H Control panel I Supply air fan J Extract air fan K Electric reheater hot water L Cooling coil with changeover M Supply air damper N Exhaust air damper Legend 1 Actuator outdoor air extr...

Страница 9: ...er end position Filters Correct filter type Are the filters correctly installed Pressure differential gauge Correct operation Pressure differential switch Correct operation set up Heaters Hot water co...

Страница 10: ...of a single skin flexible connection is 170 mm but a flexible connection must NOT be installed stretched between the AHU and the duct Once installed the operating length of the flexible connection mus...

Страница 11: ...to prevent that mist causes the filters to become too wet The pre heater will reduce the relative humidity of the air Connection of the outdoor air intake duct If condensation can be expected in or o...

Страница 12: ...further apart using an extra piece of duct at the outdoor air intake opening If the units are installed outside this piece of duct should be placed between the air handling unit and the pre installed...

Страница 13: ...e moisture Condensate may form in the period before the first start up of the AHU as a result of weather change and or humid air from the building Remove all condensate from the construction component...

Страница 14: ...pump the installation must be designed to compensate for the required heat during the system heat pump defrost cycle and the heat cannot be drawn from the supply air Otherwise the supply air temperatu...

Страница 15: ...is best to use an infinitely variable controller for the compressor condensing unit If the condensing unit has infinitely variable control one of the temperature controls in the controller can be sele...

Страница 16: ...heat recovery wheel is supplied with rotor control included in the central control panel The rotation monitor for the rotor is pre installed and connected If required the heat recovery wheel can incl...

Страница 17: ...cked open This warning also important for safety Because of the positive pressure fan doors can hit the technical personel who is opening the doors Before openning the doors the fan must be switched o...

Страница 18: ...n can rotate depends on the motor impeller assembly and should normally be higher than 50 Hz The maximum frequency is given on the fan name plate Plug fans are equipped with a pressure measurement poi...

Страница 19: ...from the building Remove all condensate from the construction components and dry the electrical components using warm dry air e g with a hair drier Do not work on electrical components including contr...

Страница 20: ...32 32 16 63 63 63 63 100 100 1 260 1 260 1 260 1 260 2 000 2 000 5 5 5 5 5 5 7 5 7 5 11 5 5 7 5 11 7 5 11 11 32 40 63 40 63 63 4 32 32 32 640 640 640 1 1 1 1 2 2 1 1 2 2 2 2 16 16 25 4 32 32 32 32 63...

Страница 21: ...connected to the control panel after the unit has been installed In the control diagram this sensor is shown as 23TT22 TT6 Room temperature sensor The passive PT1000 sensor includes room temperature...

Страница 22: ...ol damper will open if the water temperature measured is below 20 C Heating mode detection if the measured water temperature is higher than the sum of the setting values at the bottom and top dials se...

Страница 23: ...inspections and maintenance of the AHU On the following pages there is a more detailed description of the individual components WARNING Remember to deenergise all components and to ensure that the fan...

Страница 24: ...installed in the correct manner 6 6 Dampers Lubrication of the dampers is not required Remove excess contamination by cleaning with compressed air and possible cleaning with water and a mild household...

Страница 25: ...Heat recovery wheel Check the rotor once a year for contamination and if necessary clean with compressed air Check the rotor speed and compare it with the design data Check the operation of the rotati...

Страница 26: ...gn of bearing wear but also of incorrect operation of the transmission or an unbalanced system The following points require extra attention Check for vibration Check the rotation direction Avoid unnec...

Страница 27: ...Silencers It is recommended to check the splitters of the silencers periodically for possible damage and loosening of the fibres to prevent dirt deposits in the system 6 16 Control The control must b...

Страница 28: ...ERE THE AHU S POWER SUPPLY FIND THE SWITCH WHICH BELONGS TO AHU S POWER SUPPLY OPEN THE SWITCH 5 PUT THE LOCK BACK NOTE AT THE 3 STAGES SWITCHES 2 AUTOMATION 1 MANUEL CONTROL 0 MEANS CLOSE PINBOARD PI...

Страница 29: ...NOT TOUCH THE PIPES 4 CLOSE THE ELECTRICAL HEATER MAIN SWITCH SWITCH WILL BE SET FROM 1 TO 0 POSITION LOCK THE ELECTRICAL HEATER MAIN ELECTRIC SWITCH 5 CLOSE THE MAIN HEATER WATER VALVE CLOSE THE MAI...

Страница 30: ...Order No 13938 11 07 2016 Supersedes order No 13938 11 07 2014 Manufactured by Alarko Carrier Gebze Turkey The manufacturer reserves the right to change the specification without prior notice...

Отзывы: