GAS MULTIBLOCK MBC 700VEF MBC 1200 VEF SETTINGS
41
FREE GAP NEED FOR EASY FILTER CHANGE
MBC-700-VEF: (L) 170 mm
MBC-1200-VEF: (L) 230 mm
Inspect the filter at least once a year.
Change filter if ∆p between pressure connections 1 and 2 > 10
mbar.
Change the filter if ∆p the pressure connections 1 and 2 is
twice as high compared to the last inspection.
1. Interrupt gas supply: close ball valve.
2. Remove screws 1 – 2 (Figure 1).
2. Change filter insert 3.
3. Screw in screws 1 – 2 without using any force and fasten.
4. Perform leakage and function test P
max
= 360 mbar
CHANGING SOLENOID MBC-700
1. Interrupt gas supply, switch oıff power supply.
2. Undo locking screw A (Figure 2).
3. Remove cover B (Figure 3).
4. Exchange solenoid (Figure 4). Always check solenoid
No. And voltage.
5. Replace cover B, tighten by hand (Figure 3).
6. Screw in locking screw A to stop (Figure 2).
L
3
2
1
Figure 1
Figure 2
Figure 3
Figure 4
A
B
Содержание ALG 120/M
Страница 2: ...Code A 6 1 5i Revision Date 071116 Print Date 071116...
Страница 3: ...ALARKO Models ALG 200 M ALG120 M Natural Gas LPG Burners ASSEMBLY OPERATION MAINTENANCE...
Страница 16: ...16 DIMENSIONS mm ALG 200 M ALG 200 M LPG ALG 200 M ALG 200 M LPG ALG 120 M ALG 120 M LPG...
Страница 26: ...26...
Страница 34: ...2 34 VALVE PROVING SYSTEM VPS 504 SO2 Dimensions Lockout Run...
Страница 53: ...53 WIRING DIAGRAMS RWF50 ALG 200 M and ALG 200 M LPG...
Страница 54: ...54 WIRING DIAGRAMS RWF50 ALG 120 M and ALG 120 M LPG...
Страница 55: ...WIRING DIAGRAMS SDC 12 31 ALG 200 M and ALG 200 M LPG...
Страница 56: ...56 WIRING DIAGRAMS SDC 12 31 ALG 120 M and ALG 120 M LPG...