AIR FLOW ADJUSTMENT
Combustion air is taken into the burner through air
suction cell. Air flow amount is adjusted by an air
damper placed in this cell. The damper is run by
damper motor (See Figure on the right). 0 value on the
indicator means the damper is fully closed, 9 value
means fully opened. Air damper motor adjustment is
told in an other section of this manual.
Decrease the air flow to minimum value for
the first running of the burner. Make the
adjustments of the air damper following the
combustion start.Air flow adjustment is
made with the damper motor shafts for
modulating burners. Check if the burner
start is OK after completing the air flow
adjustments.
The correct position of the air damper for
the desired burner capacity can be found
using the graphs given on this page.
These graphs are derived in laboratory
conditions and are for avarage values. The
positioning values may vary according to
different boiler conditions. Therefore the
final adjustment must be done by the
evaluation of the flue gas emissions on
site.
Proper emissions are given as follows;
CO < 93 ppm
ג
≤ 1,2 (for max capacity)
ג
≤ 1,5 (for min capacity )
NOx ≤ 83 ppm
ג
:
E
xcess air ratio
19
ENERJÝ BESLEMESÝ:
..... - ........
KAPASÝTE:
ISI YÜKÜ :
SERÝ NO :
**
ÜRETÝM YILI :
kW
*
XX
ALG 200/M
TÝP :
Gebze - KOCAELÝ
SANAYİ VE TİCARET A.Ş.
Tel: (0262) 648 60 00
Þahabettin Bilgisu Cad. 41480
ALARKO CARRIER
GOSB - Gebze Organize Sanayi Bölgesi
ALG 200/M
1
3
5
7
9
800
1000
1200
1400
1600
1800
Capacity (kW )
A
ir
D
am
p
er
P
o
si
ti
o
n
ALG 200/M (LPG)
1
3
5
7
9
800
1000
1200
1400
1600
1800
Capacity (kW)
A
ir
D
am
p
er
P
o
si
ti
o
n
ALG 120/M
0,5
2,5
4,5
6,5
8,5
400
500
600
700
800
900
1000
1100
1200
1300
Capacity (kW )
A
ir
D
am
p
er
P
o
si
ti
o
n
ALG 120/M (LPG)
0,5
1
1,5
2
2,5
3
3,5
400
500
600
700
800
900
1000
1100
1200
1300
Capacity (kW )
A
ir
D
am
p
er
P
o
si
ti
o
n
Содержание ALG 120/M
Страница 2: ...Code A 6 1 5i Revision Date 071116 Print Date 071116...
Страница 3: ...ALARKO Models ALG 200 M ALG120 M Natural Gas LPG Burners ASSEMBLY OPERATION MAINTENANCE...
Страница 16: ...16 DIMENSIONS mm ALG 200 M ALG 200 M LPG ALG 200 M ALG 200 M LPG ALG 120 M ALG 120 M LPG...
Страница 26: ...26...
Страница 34: ...2 34 VALVE PROVING SYSTEM VPS 504 SO2 Dimensions Lockout Run...
Страница 53: ...53 WIRING DIAGRAMS RWF50 ALG 200 M and ALG 200 M LPG...
Страница 54: ...54 WIRING DIAGRAMS RWF50 ALG 120 M and ALG 120 M LPG...
Страница 55: ...WIRING DIAGRAMS SDC 12 31 ALG 200 M and ALG 200 M LPG...
Страница 56: ...56 WIRING DIAGRAMS SDC 12 31 ALG 120 M and ALG 120 M LPG...