AL-KO air heater / air cooler DESIGN
Retrofitting of a heating-only heater for cooling operation requires the following:
1
Condensate pump
2
Fastening screw
3
Fastening plate
4
Reinforcement of cover panel
Fasten the condensate pump (Pos. 1) and the fastening plate (Pos. 3) with the fastening screw (Pos. 2) to the rein-
forcement of the cover panel (Pos. 4).
Thereafter, insert the filling level sensor (DrainStick) with the condensate extraction hose and the cable through the
cover sheet.
Electrical connection according to the regulations.
1
Filling level sensor with condensate extraction hose and cable
2
Electrical connection
Cut the attached hose to a length of 60 mm and push it over the DrainStick.
The filling level sensor with the condensate extraction hose and the cable must be fastened on the inside of the hood
with the fastening bases and cable binders supplied.
The extraction opening of the condensate hose must be fastened at the deepest part of the hood and as close as
possible to a vertical position.
The alarm contact must be located below the level of the (full) hood.
The installation should be arranged as shown in the figure below.