Subject to changes in line with technical progress!
91
3468161
Commissioning
1
2
3
Fig. 62 Example for gap dimension (depending on the manufacturer)
1
Impeller
2
Inlet nozzle
3
Gap dimension gauge
NW Nominal width (nozzle)
D1
Inner diameter (cover disc nozzle of the impeller)
D2
Outer diameter (inlet nozzle)
s
min
With test gauge for gap width to be ensured
ü
Coverage
Step
Action
1
Check the gap dimension between the impeller and inlet nozzle according to the fan manufacturer documentation. En
-
sure that the gap dimension is not underrun during any phase of the rotary movement (turning by hand). For the valid
measured values, see the documentation of the fan manufacturer.
2
Measure the gap dimension at four points m circumference offset by 90°. Place the supplied gauge to the outer diame
-
ter of the inlet nozzle. The minimum gap must not be underrun. The gauge must not jam, slight rubbing of the impeller
during rotation is permissible.
3
The fan may only be operated if the test has been passed.
Document the test results.
ATTENTION
Risk of ignition due to impermissible gap dimensions between stationary and rotating com-
ponents.
Ensure that the gap does not fall below the valid gap dimension at any point.
ATTENTION
Observe the manufacturer's documentation.