27
The genset should run 2-3 minute with no load.
Selecting
STOP O
position, de-energises the
fuel solenoid, bringing the generator to a stop.
9.2 At Automatic Models:
To control and monitor the generating set, an
electronic control system has been used.
Depending on the requirements of the set, one
of several different standard control systems may
be fitted. These include ME 40 Model Manual
Control panel or P 500, P2020 Auto Mains Failure
panel and 2010 Autostart Panel Control panel
provides a means of starting and stopping the
generating set, monitoring its operation and
output, and automatically shutting down the set
in the event of a critical condition arising such as
low oil pressure or high engine temperature.
10. GENERATING SET
CONTROL SYSTEMS
10.1 CONTROL PANELS
Control, supervision and protection panels are
mounted on the generator base frame.
10.2 MANUAL CONTROL SYSTEM - ME 40
10.2.2 DSE 701 MODULE EMERGENCY LEDs
High engine temperature, shutdown
Low oil pressure, shutdown
Over speed, shutdown
Charge failure, warning
10.2.1 DSE 701 MODULE FEATURES
Engine supervision and protection
Key switch operation on the fron panel
Figure 10.2
DSE 701 Manuel Control Module
Figure 10. 1
ME 40 Manual Control Panel
Control with DSE 720 Automatic Mains
Failure module
Static battery charger
Emergency stop push button
10.3 Control System P300 Panel
Specifications:
10.3.1 DSE 720 Module features:
To monitoring AC mains supply
Automatic controls generating set, start
and stop
Provide signal to change over switch
Scrolling digital LCD display
Front panel configuration of timers and
alarm trip points
Easy push button control
STOP/RESET MANUAL AUTO
TEST START
LCD display Scroll push button
Control with DSE 701 Module
3 Ammeters
1 Hours run meter
1 Volt - Frequencymeter (by LED) and
selector switch
Engine oil pressure gauge
Engine coolant temperature gauge
Emergency stop push button
3 pole alternator circuit braker