20
Tablo 4.7.1
Recommended cable cross sections (50 Hz, Gen-sets).
Note
: PVC isolated cables YVV suitable to 0,6/1kV VDE norms and TSE
GENERATING SETS
ALP 8
ALP 12
ALP 15
ALP 16
ALP 22
ALP 30
AP 500
AP 550
Model
8
12
15
16.5
22
30
500
550
25
25
25
34
34
60
855
855
4 x 2.5
4 x 2.5
4 x 2.5
4 x 4
4 x 4
4 x 10
3 x (3 x 120 / 70)
3 x (3 x 120 / 70)
Stand by
Power
(kVA)
Current
Capacity of
Cable at Air
(Ampere)
Cable Section
YVV 25 ºC
(mm
2
)
Lister Petter
Perkins
12
17
21
23
31
43
720
792
Full Load
Current
U=400 Vac
Cos
j
: 0,8
GENERATING SETS
ALP 10-6
ALP 15-6
ALP 21-6
AP 565-6
AP 616-6
Model
Full Load
Current
U=400 Vac
Cos
j
: 0,8
Current
Capacity of
Cable at Air
(40°C ambient
temperature)
(Ampere)
Lister Petter
10
15
21
565
616
14.4
21.6
30
816
890
22
30
38
1068
1068
2.5
4
6
4x120
4x120
Stand by
Power
(kVA)
Cable Section
(NYY) Single core
for each phase
(mm
2
)
Perkins
Table 4.7.2
Recommended cable cross sections (60 Hz, Gen-sets).
Note :
PVC isolated cables YVV suitable to 0,6/1 kV, VDE norms and TSE