1.- Versions
2.- Cautions
-Using the unit not observing the manufacturer's instructions may alter the appliance safety requirements. Only
probes supplied by AKO should be used for the unit to operate correctly.
2
-From -40 ºC to +20 ºC, if the NTC probe is extended to 1000 m with at least 0.5 mm cable, the maximum
deviation will be 0.25 ºC (cable for probe extension ref. AKO-15586).
-Only NTC probes supplied by AKO should be used for the appliance to operate correctly.
-Should be installed in a place protected from vibrations, water and corrosive gases, where the ambient
temperature does not exceed the value indicated in the technical data.
-For the reading to be correct, the probe should be used in a place without heat influences apart from the
temperature you want to measure or control.
-Always disconnect the power supply to do the wiring. The power supply circuit should have a main switch and
residual current protection outside the panel (according to 2 2 R.E.B.T.). The power supply cable will be H05VV-F
2
2
2x2.5 mm or H05V-K 2x2.5 mm .
2
-Cables for relay or contactor outputs should have a section of 2.5 mm , allow working temperatures equal to or
over 70 ºC and be installed with as few bending as possible.
-The length of probe cables and the digital inputs must not exceed 30 metres.
-IP65 protection degree is only valid with the protection cover closed.
-IP65 protection degree is only valid if the cables enter the device using a tube for electric condu gland
with IP65 or above. The gland should be the right size for the diameter of the tube used.
3.- Wizard
The
PROPlus Basic
and
CAMCtrl Basic
units have a programming wizard that configures
the equipment depending on the selected control type. The different options are displayed
in the table, the rest of parameters will be configured according to the “
Def
” column of the
parameter table (See page 27).
This wizard only starts the first time the device is powered up, displaying the text
P3
on screen.
To restart the wizard after the initial configuration, restart the controller (turning the power supply on and off) and
before 8 seconds have passed, press the following sequence of keys in the indicated order:
N
,
Q
y
SET.
DEFAULT SETTINGS BY CONTROL TYPE (P3)
WARNING:
The default parameters by type of application have been defined for the most common
applications. Check that these parameters are suitable for your installation.
P3=1:
Service box
P3=2:
Pump down active
P6:
AUX relay 1 configuration
1
: Light
2
: Pump down
P62:
AUX relay 2 configuration
2
: Alarm
1
: Light
P10:
Digital input 1 configuration
0
: Off
6
: Low pressure switch
P12:
Digital input 1 polarity
0
: Energised on closed contact
1
: Energised on open contact
MODELS
DESCRIPTION
POWER SUPPLY
COND.
UN.
230 V/I
EVAP.
FAN
230 V/I
DEFROST
CIRCUIT BREAKER
PROTECTION
MODBUS
COMM.
T.P.
ALARM
230 V/I
400 V/III
AKO-15626
CAMCtrl Basic
230 V ±10%
50 Hz ±5 Hz
11 A
3 A
2.500 W
-
No
Yes
NO
AKO-15627
Yes
AKO-15645
PROPlus Basic 1F
16 A
NO
AKO-15646
Yes
AKO-15648
PROPlus Basic 3F
400 V ±10%
50 Hz ±5 Hz
9 A
-
5.500 W
16 A (Power Supply)
10 A / III (Defrost)
NO
17