Level 1.- DIGITAL INPUT CONFIGURATION
Level 1.- ENERGY SAVING CONFIGURATION
Description
Units
Min
Def
Max.
I01
Polarity digital input 1 (thermal stage 1):
0
=Activates on closing contact;
1
=Activates on opening contact
0
0
1
I02
Polarity digital input 2 (thermal stage 2):
0
=Activates on closing contact;
1
=Activates on opening contact
0
0
1
I03
Polarity digital input 3 (thermal stage 3):
0
=Activates on closing contact;
1
=Activates on opening contact
0
0
1
I04
Polarity digital input 4 (thermal stage 4):
0
=Activates on closing contact;
1
=Activates on opening contact
0
0
1
I05
Polarity digital input 5:
0
=Activates on closing contact;
1
=Activates on opening contact
0
0
1
I06
Polarity digital input 6:
0
=Activates on closing contact;
1
=Activates on opening contact
0
0
1
I07
Digital input 5 function:
0
=Low pressure alarm
1
=High pressure alarm
2
=Thermal stage alarm 5
3
=Ambient temperature probe
4
=External alarm
5
=Remote disconnection ON-OFF
6
=Variation in the aspiration set point (E01)
(see remark 2)
0
0
6
I08
Digital input 6 function:
0
=Low pressure alarm
1
=High pressure alarm
2
=Thermal stage alarm 5
3
=Ambient temperature probe
4
=External alarm
5
=Remote disconnection ON-OFF
6
=Variation in the aspiration set point (E01)
(see remark 2)
0
1
6
I09
Turn-on delay time of digital input 5 (not applicable if
I07
=2)
sec.
0
0
255
I10
Retardo de activación de la entrada digital 6 (No aplica si
I08
=2)
sec.
0
0
255
I11
Variation in the evaporation set point (new set point= E01+I11)
(see remark 2)
bar
-20
0
20
I12
Duration of the variation in the evaporation set point
(see remark 2)
min.
0
0
255
EP
Output to level 1
Description
Units
Min
Def
Max.
S01
Start of energy saving - Day of the week:
0
=Deactivated
1
=Monday
2
=Tuesday
3
=Wednesday
4
=Thursday
5
=Friday
6
=Saturday
7
=Sunday
8
=Monday to Sunday
9
=Monday to Saturday
10
=Monday to Friday
11
=Saturday to Sunday
0
0
11
S02
Start of the energy saving - Hour
(see remark 2)
h.
0
0
23
S03
Start of the energy saving - Minute
(see remark 2)
min.
0
0
59
S04
Duration of the energy saving
(see remark 2)
h.
0
0
24
S05
Variation in the evaporation set point during energy saving
(E01+S05)
(see remark 2)
bar
-20
0
20
EP
Output to level 1
Level 2
Level 2
Remark 2:
In the event of the energy saving and the variation in the set point per digital input being activated at the
same time, the variation in the set point per digital input will always prevail.
21
1454H502 Ed.03