Level 1.- CONDENSATION CONFIGURATION
Level 1.- PROBE CONFIGURATION
Description
Units
Min
Def
Max.
F01
Condensation pressure / temperature set point
bar
F03
19
F02
F02
Condensation set point upper limit (It cannot be set above this limit)
bar
F03
75
75
F03
Condensation set point lower limit (It cannot be set below this limit)
bar
-0.7
-0.7
F02
F04
Fan rotation type:
0
=Balancing, depending on the operation time
1
=Sequential (the last in is the first out)
0
1
1
F05
Fan control type:
0
=Neutral zone;
1
=Proportional
0
0
1
F06
Condensation regulation bandwidth
bar
0.0
2.0
50
F07
For fans when the compressors stop
0
=No;
1
=Yes
0
0
1
F08
Floating condensation
0
=No;
1
=Yes
0
0
1
F09
Integral time (PID inverter control)
sec.
2
5
10
F10
Floating condensation minimum set point value
( see remark 1)
ºC
-50
28
99.9
F11
Condenser temperature delta
ºC
6
12
20
EP
Output to level 1
Description
Units
Min
Def
Max.
P01
Probe type selection
0
=4-20 mA;
1
=0-5 V;
2
=NTC
0
0
2
P02
Probe to be displayed:
0
=Probe 1 (Aspiration)
1
=Probe 2 (Discharge);
2
=Probes 1 and 2 in carousel
0
0
2
P03
Value 4 mA / 0 V (according to P01) probe 1
bar
-60
-60
999
P04
Value 20 mA / 5 V (according to P01) probe 1
bar
-60
999
999
P05
Probe 1 calibration (Offset)
bar
-20
0
20
P06
Value 4 mA / 0 V (according to P01) probe 2
bar
-60
-60
999
P07
Value 20 mA / 5 V (according to P01) probe 2
bar
-60
999
999
P08
Probe 2 calibration (Offset)
bar
-20
0
20
P09
Calibration of the outside temperature probe for floating condensation
ºC
-20
0
20
EP
Output to level 1
Level 2
Level 2
Remark 1:
The equivalent value in pressure is calculated depending on the refrigerant gas specified in the wizard.
20