Model No.: AC-S7CG 
Version: 1.0 

 

   

 
 

f.  Defrosting conditions and procedures 

i.  In heating mode, if compressor has run 44 minutes ( in its first 6 minutes it will not detect 

defrosting temp.) , and it has detected T con < or = -4

o

C for continuous 1 minutes, it begins 

to defrost, electric heater will stop for 10 seconds ( even if electric heater is not working), 
then indoor motor stops, reversing valve becomes inactive in another 2 seconds, another 2 
seconds later, outdoor motor stops, when T con > or = 10

o

C or defrosting lasts for 10 

minutes, outdoor motor and reversing valve becomes active, indoor motor will run as the 
anti cool air condition, then it cycles again, recalculates the compressor’s running time 
again. (In this period, if any protection works, and after the machine is back to work, it will 
re-start defrosting state. it will not detect outdoor tube temp when compressor’s in its first 6 
minutes running) 

g.  Noise eliminated protection 

i.  When you use RUN/STOP button to switch off the machine, reversing valve will become 

inactive in 2 minutes. 

 

AUTO mode 

 
1  In AUTO mode, standard cooling T set = 25

o

C, standard heating T set = 20

o

C. 

2  Working procedures 

a.  If T indoor > or = T set + 1

o

C , select cooling mode, from this time, the set temp. is 25

o

C. If T 

indoor < or = T set – 1

o

C, compressor and outdoor motor stop, indoor motor runs at the set 

speed, if T set -1 < T indoor < T set + 1

o

C, keep the original state. 

b.  If T indoor < or = T set + 2

o

C, select heating mode, from this time, the set temp. is 20

o

C, if T 

indoor > or = T set + 4

o

C, compressor stops first, outdoor motor stops 15 seconds later, 

reversing valve is always active, indoor motor runs as the blowing surplus heat condition. If T 
set +2

o

C < T indoor < T set +4

o

C, keeps the original state. Cooling only AUTO mode: there is 

no heating function in this mode. 

3  Protections 

a.  It is same as the one in cooling or heating mode. 

 
4  Other controls 

1  SWING mode 

a.  When it is active, the louver returns to position O, close the air outlet. 
b.  When machine works, it turns to the max. Air output position D, then returns back to position L 

to stand by (position L is the horizontal place mentioned before). 

c.  In swing state, the louver swings between position L and position D. 
d.  When the machine is switched off, it is back to position O. 
e.  When the machine is running and the swing is off, the louver stops at position E. 

 
                                                      O 
 
 
 
 
 
 
 
 
 
                                                                                                                            L 
                                                                                                                             
 
 
 
                                                                                                                  E 
                                                                                        D 
 
 

Все каталоги и инструкции здесь:

 http

:

//splitoff.ru/tehn-doc.html

Содержание AC-S7CG

Страница 1: ...Air Conditioner Service Manual Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...

Страница 2: ...2 Model No AC S7CG Version 1 0 MODEL AC S7CG Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 3: ... No AC S7CG Version 1 0 CONTENTS TECHNICAL SPECIFICATION 4 PERFORMANCE CURVE 5 EXPLODED VIEW PARTLIST 8 CIRCUIT DIAGRAM 12 PCB FUNCTION MANUAL 13 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 4: ... CFM Hi M3 H 400 Air Flow control Remarks Ventilation No Exhaust No Energy saver switch No Dimension W x H x D mm indoor 740 x 250 x 180 Dimension W x H x D mm outdoor 660 x 428 x 255 Packing Dimension W x H x D mm indoor 870 x 336 x 280 Packing Dimensions W x H x D mm outdoor 765 x 500 x 350 Indoor Weight net Gross kg 8 11 Outdoor Weight Net Gross kg 25 29 Все каталоги и инструкции здесь http spl...

Страница 5: ...etween low pressure operation current and temp Cooling operation condition In testing indoor and outdoor have same work condition Heating operation Indoor work condition dry bulb temp 21 wet bulb temp 15 5 o C Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 6: ...6 Model No AC S7CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 7: ...7 Model No AC S7CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 8: ...8 Model No AC S7CG Version 1 0 EXPLODED VIEW PART LIST INDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 9: ... 18 Filter 2 19 Air cleaner holder 2 20 Guide louver 1 21 Remote controller Y512F 1 22 Guide louver bearing 3 23 Main PCB 1 24 Fuse 3 15A250VAC 1 25 Room sensor 1 26 Tube sensor 1 27 Sensor insert 1 28 Sensor motor MP28EA 1 29 Motor FN7C 1 30 Motor clamp 1 31 Wire clip 1 32 Wire clamp 1 33 LED holder 1 34 Receiver board JD 1 35 Receiver board K 1 36 Terminal board T240A 1 37 Electric box cover 1 3...

Страница 10: ...10 Model No AC S7CG Version 1 0 OUTDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 11: ... Compressor KH145VFRA 1 10 Overload protector 1 11 Handle 1 12 Gas valve 1 13 Liquid valve 1 14 Valve support 1 15 Right side plate 1 16 Wiring clamp plate 1 17 Wiring clamp cover 1 18 Terminal board T386A 1 19 Electric plate 1 20 Comp capacitor 1 21 Capacitor clamp 1 22 Fan capacitor 1 23 Isolation sheet assy 1 24 Condenser assy 1 25 Rear grill 1 Все каталоги и инструкции здесь http splitoff ru t...

Страница 12: ... No AC S7CG Version 1 0 CIRCUIT DIAGRAM These circuit diagrams are subject to change without notice Please refer to the ones stuck on the machines Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 13: ... keep the previous state 2 In this mode the reversing valve is inactive the temp setting range is from 16 30o C 3 Protect function a Anti freezing function i If compressor have run 6 minutes and detect T eva 0o C for continuous 3 minutes then the compressor outdoor fan stopped indoor fan run at the set fan speed After 3 minutes later it will run at the original state if T eva or 10o C b Compressor...

Страница 14: ...ing state 2 In this mode the temperature setting range is 16 30o C 3 The working conditions of auxiliary electric heater a In heating mode when compressor is working indoor motor runs at high speed and middle speed If it detect T eva 50o C for continuous 8 seconds and T indoor or 25o C electric heater will work if compressor stop or indoor motor runs at low speed or T eva 54o C or T indoor 28o C o...

Страница 15: ...standard heating T set 20o C 2 Working procedures a If T indoor or T set 1o C select cooling mode from this time the set temp is 25o C If T indoor or T set 1o C compressor and outdoor motor stop indoor motor runs at the set speed if T set 1 T indoor T set 1o C keep the original state b If T indoor or T set 2o C select heating mode from this time the set temp is 20o C if T indoor or T set 4o C comp...

Страница 16: ...IR on the remote controller to select fresh air 1 function the swing motor keeps running till you give a signal to change it 6 Automatic fan speed a In cooling mode if T indoor T set 5o C high speed T indoor or T set 3o C middle speed T indoor or T set 1o C low speed b In dehumidify mode if T indoor or T set 5o C high speed T indoor or T set 2o C low speed SLEEP mode 1 In cooling or dehumidifying ...

Страница 17: ...Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...

Отзывы: