akira AC-S7CG Скачать руководство пользователя страница 14

   

   

 

 

 

 

 

 

 

 

                         

14

   

 
Model No.: AC-S7CG 
Version: 1.0 

 

   

 
 

Dehumidifying mode 

 

1  The working conditions and control measures 

a.  If T in > T set + 2

o

C, it is in cooling running, the indoor motor speed can be selected, and 

outdoor motor run at low speed. 

b.  If T set – 2

o

C < or = T in < or = T set + 2

o

C, it goes into dehumidifying running, the indoor motor 

run at the low speed, 6 minutes later the compressor stops, another 15 seconds later the outdoor 
fan stops and another 30 seconds later, the indoor motor stops, 3 and a half minutes later, 
compressor and outdoor fan run again, indoor motor runs at the low speed, then the machine 
cycle the above procedures repeatedly. Outdoor motor runs at the low speed. 

c.  If T in > T set – 2

o

C, compressor, outdoor motor and indoor motor stop. 

2  In this mode, the reversing valve is inactive, the temp. setting range is 16~30

o

C. 

3  Anti-freezing protection. 

a.  If T indoor > T set + 2

o

C, it goes into cooling running, anti-freezing function is same with 

cooling mode, but the compressor must stops for 4 minutes when it goes into dehumidifying 
mode, compressor runs 6 minutes, if it detects T eva < 0

o

C, compressor and outdoor motor stop, 

indoor motor runs at low speed, after 3 minutes delay, and T eva > or = 10

o

C, it will be back to 

its original state. 

 

Heating mode 

 
1  The working conditions and control measures 

a.  If T in < or = T set + 2

o

C, it goes into heating mode, reversing valve, compressor and outdoor   

motor all work in the same time, indoor fan will run at the same procedures with anti cool air 
function. 

b.  If T in > or = T set + 4

o

C, compressor stops first, 15 seconds late, outdoor motor stops, but 

reversing valve keeps working, indoor motor run at the procedures of blowing surplus heat. 

c.  If T set + 2

o

C < T indoor < T set + 4

o

C, keep the previous running state. 

2  In this mode, the temperature setting range is 16~30

o

C. 

3  The working conditions of auxiliary electric heater. 

a.  In heating mode, when compressor is working, indoor motor runs at high speed and middle 

speed. If it detect T eva < 50

o

C for continuous 8 seconds and T indoor < or = 25

o

C , electric 

heater will work, if compressor stop or indoor motor runs at low speed or T eva 54

o

C or T indoor 

28

o

C or 10 seconds before defrosting, the electric heater will stop. 

4  Protections 

a.  Anti cool air 

i.  When the machine starts heating and T eva > or = 22

o

C , indoor motor runs at low speed, 

and swing motor makes the louver at the horizontal position, if T eva > or = 40

o

C or 

compressor have run 2 minutes ,indoor motor and swing motor will run at the set speed. 

b.  Anti high temp. 

i.  In heating mode, if it detect T eva 56

o

C (58 can be selected), outdoor motor will stop (in this 

period it will not detect the defrosting temp.). If T eva 52

o

C, outdoor motor will be back 

running (it will not detect defrosting temp. in the first 5 seconds). 

c.  Blowing surplus heat 

i.  In heating mode, when set temp is reached, comp. stops first, 15 seconds later outdoor fan 

stops, Indoor motor blows 90 seconds (60 seconds can be selected) at low speed ,swing 
motor makes the louver at the horizontal position. 

d.  Compressor’s protection is same with the one in cooling mode. 
e.  Overload protection 

i.  If it detects that the system current surpassed the designed 13 A for continuous 3 seconds, 

compressor, electric heater and outdoor motor stop , indoor motor runs the same procedures 
as the blowing surplus heat condition. After 3 minutes and current no more than 13 A, the 
machine will be back to its original state, indoor motor runs as the anti cool air condition. If 
it detects overloading state for 3 consecutive times within 30 minutes, the machine stops, 
and it must be restarted by remote controller. 

 
 
 

Все каталоги и инструкции здесь:

 http

:

//splitoff.ru/tehn-doc.html

Содержание AC-S7CG

Страница 1: ...Air Conditioner Service Manual Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...

Страница 2: ...2 Model No AC S7CG Version 1 0 MODEL AC S7CG Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 3: ... No AC S7CG Version 1 0 CONTENTS TECHNICAL SPECIFICATION 4 PERFORMANCE CURVE 5 EXPLODED VIEW PARTLIST 8 CIRCUIT DIAGRAM 12 PCB FUNCTION MANUAL 13 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 4: ... CFM Hi M3 H 400 Air Flow control Remarks Ventilation No Exhaust No Energy saver switch No Dimension W x H x D mm indoor 740 x 250 x 180 Dimension W x H x D mm outdoor 660 x 428 x 255 Packing Dimension W x H x D mm indoor 870 x 336 x 280 Packing Dimensions W x H x D mm outdoor 765 x 500 x 350 Indoor Weight net Gross kg 8 11 Outdoor Weight Net Gross kg 25 29 Все каталоги и инструкции здесь http spl...

Страница 5: ...etween low pressure operation current and temp Cooling operation condition In testing indoor and outdoor have same work condition Heating operation Indoor work condition dry bulb temp 21 wet bulb temp 15 5 o C Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 6: ...6 Model No AC S7CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 7: ...7 Model No AC S7CG Version 1 0 Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 8: ...8 Model No AC S7CG Version 1 0 EXPLODED VIEW PART LIST INDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 9: ... 18 Filter 2 19 Air cleaner holder 2 20 Guide louver 1 21 Remote controller Y512F 1 22 Guide louver bearing 3 23 Main PCB 1 24 Fuse 3 15A250VAC 1 25 Room sensor 1 26 Tube sensor 1 27 Sensor insert 1 28 Sensor motor MP28EA 1 29 Motor FN7C 1 30 Motor clamp 1 31 Wire clip 1 32 Wire clamp 1 33 LED holder 1 34 Receiver board JD 1 35 Receiver board K 1 36 Terminal board T240A 1 37 Electric box cover 1 3...

Страница 10: ...10 Model No AC S7CG Version 1 0 OUTDOOR UNIT Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 11: ... Compressor KH145VFRA 1 10 Overload protector 1 11 Handle 1 12 Gas valve 1 13 Liquid valve 1 14 Valve support 1 15 Right side plate 1 16 Wiring clamp plate 1 17 Wiring clamp cover 1 18 Terminal board T386A 1 19 Electric plate 1 20 Comp capacitor 1 21 Capacitor clamp 1 22 Fan capacitor 1 23 Isolation sheet assy 1 24 Condenser assy 1 25 Rear grill 1 Все каталоги и инструкции здесь http splitoff ru t...

Страница 12: ... No AC S7CG Version 1 0 CIRCUIT DIAGRAM These circuit diagrams are subject to change without notice Please refer to the ones stuck on the machines Все каталоги и инструкции здесь http splitoff ru tehn doc html ...

Страница 13: ... keep the previous state 2 In this mode the reversing valve is inactive the temp setting range is from 16 30o C 3 Protect function a Anti freezing function i If compressor have run 6 minutes and detect T eva 0o C for continuous 3 minutes then the compressor outdoor fan stopped indoor fan run at the set fan speed After 3 minutes later it will run at the original state if T eva or 10o C b Compressor...

Страница 14: ...ing state 2 In this mode the temperature setting range is 16 30o C 3 The working conditions of auxiliary electric heater a In heating mode when compressor is working indoor motor runs at high speed and middle speed If it detect T eva 50o C for continuous 8 seconds and T indoor or 25o C electric heater will work if compressor stop or indoor motor runs at low speed or T eva 54o C or T indoor 28o C o...

Страница 15: ...standard heating T set 20o C 2 Working procedures a If T indoor or T set 1o C select cooling mode from this time the set temp is 25o C If T indoor or T set 1o C compressor and outdoor motor stop indoor motor runs at the set speed if T set 1 T indoor T set 1o C keep the original state b If T indoor or T set 2o C select heating mode from this time the set temp is 20o C if T indoor or T set 4o C comp...

Страница 16: ...IR on the remote controller to select fresh air 1 function the swing motor keeps running till you give a signal to change it 6 Automatic fan speed a In cooling mode if T indoor T set 5o C high speed T indoor or T set 3o C middle speed T indoor or T set 1o C low speed b In dehumidify mode if T indoor or T set 5o C high speed T indoor or T set 2o C low speed SLEEP mode 1 In cooling or dehumidifying ...

Страница 17: ...Большая библиотека технической документации http splitoff ru tehn doc html каталоги инструкции сервисные мануалы схемы ...

Отзывы: