After Sales Support 1300 886 649
Compressor doesn’t work.
Check whether the indoor temperature is lower than 15°C or larger than.
Check whether the voltage is too high or too low.
Check whether the compressor is under overload protection.
Check the power supply.
Check the wiring.
Check whether the relay of compressor in PCB works normally (Start the
unit, after 3mins, and set the unit with cool mode and 17°C (62°F). Then
check the output of relay and replace the PCB if failed.
Check whether the external
protector works normally.
Remove the overload protector and
cool to normal temperature. Then check
whether it is open circuit. Replace if failed.
Comparing with compressor specification, check the resistance of compressor.
Replace the compressor.
No
No
No
No
No
No
No
No
Yes