25
The table below shows all the error codes displayed on the remote controller fitted in the
AWS control panel. In case of malfunction contact the AISIN Authorised Service Centre that
usually maintains the GHP outdoor unit.
R/C
AWS
Blinking indication
(ON doesn’t blink)
(OFF led off)
GHP
outdoor
unit
display
Type of failure
Possible cause
Error
code
Led
ON/OFF
TEST
Disp.
Unit
No.
A0
X
X
X
63-n
External input
•
External protection input signal stops the unit
•
Remote controller local setting failure
A1
X
X
X
20-n
Indoor unit
PC board
•
PC board defective
•
EEPROM setting error
A3
X
X
X
95-n
Drain lines
-
AWS flow switch
•
Direct Expansion version – indoor unit drain pump
malfunction .
•
AWS version – flow switch or antifreeze thermostat
switched off.
A6
X
X
X
15-n
Indoor unit fan
motor
•
Fan motor blocked
•
Harness disconnection
A7
ON
X
X
35-n
Indoor unit swing
flap motor
•
Swing flap motor malfunction
•
Cam mechanism failure
A9
X
X
X
21-n
Indoor unit
PC board
•
LEV malfunction
•
Harness disconnection
AF
ON
OFF
X
30-n
Drain pipe
•
Improper drain piping installation (inverse draft)
•
Pipe clogged
AH
ON
OFF
X
31-n
Air cleaning
device
•
Indoor unit circuit boar malfunction
•
Air cleaning device failure (optional)
AJ
X
X
X
22-n
Capacity setting
•
Capacity setting failure
•
Missing capacity setting adapter (replacement of PCB)
C4
X
X
X
18-n
Indoor unit
temperature
sensors
•
Heat exchanger temperature sensor failure
•
Improper harness connection
C5
X
X
X
19-n
•
Gas pipe temperature sensor failure
•
Improper harness connection
C9
X
X
X
97-n
•
Direct Expansion version - Intake air temperature sensor
failure
•
AWS version – Resistors group failure
•
Improper harness connection
CA
X
X
X
98-n
•
Exhaust air temperature sensor failure
•
Improper harness connection
CJ
ON
OFF
X
17-n
R/C temperature
sensor
•
R/C temperature sensor failure
•
Improper harness connection
U3
X
X
X
-
Test run
•
Test run operation
U4
X
X
X
-
Communication
•
Outdoor unit power supply OFF
•
Outdoor unit – indoor unit transmission error
U5
X
X
X
1-n
Communication
•
Duplicating main remote controller connection
•
Transmission error
OFF
ON
OFF
-
Remote
controller
PC board
•
Remote controller PC board failure
•
Remote controller setting failure
U8
X
X
OFF
-
•
Transmission error between main and sub remote
controller
U9
X
X
X
-
Communication
•
Transmission error between two indoor units
•
Transmission error between outdoor and indoor unit
UC
ON
ON
ON
36-n
Central remote
controller
•
Address duplication of central remote controller
•
Air-net address duplication of indoor units
UE
X
X
X
23-n
•
Transmission error between indoor unit and central
remote controller
UF
X
X
X
24-n
Communication
•
Communication error between indoor and outdoor unit
•
Improper wiring
UH
X
X
X
-
•
Indoor unit address setting failure
E1
X
X
X
40-0
∼
2
Outdoor unit
PC board
•
EEPROM failure or program failure
X
X
X
84-3,4
•
Outdoor unit PC board malfunction
•
Transmission error between microcomputer
E3
X
X
X
86-0
Operation failure
•
Refrigerant High pressure alarm
E4
X
X
X
88-0
•
Refrigerant Low pressure alarm
E7
X
OFF
X
86-10
∼
23
Outdoor unit fan
•
Heat exchanger fan (1,2,3) failure
•
DCBL board failure
EA
X
X
X
57-0
4-way valve
•
4-way valve failure
•
Harness disconnection
EC
X
X
X
80-0
Operation failure
•
Engine coolant overheating (temperature >105°C)
EH
X
X
X
80-10
∼
30
Engine coolant
pump
•
Engine coolant pump failure
•
DCBL board failure
Содержание AXGP224E1
Страница 1: ......
Страница 2: ...2 ...
Страница 4: ...4 ...
Страница 7: ...7 1 2 External dimensions ...
Страница 25: ...25 1 12 2 Wiring example AC 230 V single phase ...
Страница 26: ...26 1 13 Power supply wiring procedure 1 13 1 Wiring instruction ...
Страница 32: ...32 2 2 External dimensions ...
Страница 40: ...40 2 7 Outline diagram of refrigerant piping 2 7 1 Combined installation ...
Страница 41: ...41 2 7 2 Stand alone installation ...
Страница 59: ...59 2 13 Power supply wiring procedure 2 13 1 Wiring instruction combined installation ...
Страница 60: ...60 2 13 2 Wiring instruction stand alone installation ...
Страница 62: ...62 2 14 2 Wiring example AC 230V single phase ...
Страница 85: ...19 11 4 HVAC installation layout AWS E1 ...
Страница 86: ...20 11 5 HVAC installation E1 with proportional distribution of consumption ...
Страница 87: ...21 11 6 HVAC installation AWS E1J variable flow rate no hydraulic separator AHU ...
Страница 88: ...22 11 7 HVAC installation AWS E1J variable flow rate with hydraulic separator fan coil ...
Страница 93: ...27 NOTE ...
Страница 94: ...28 ...
Страница 95: ...29 ...
Страница 96: ......
Страница 109: ...13 7 2 Detailed wiring diagram ...
Страница 115: ...19 11 4 HVAC installation AWS E1J TWIN ...
Страница 116: ...20 11 5 HVAC installation E1J TWIN proportional distribution of consumption ...
Страница 117: ...21 11 6 HVAC installation AWS E1J TWIN variable flow rate no hydraulic separator AHU ...
Страница 118: ...22 11 7 HVAC installation AWS E1J TWIN variable flow rate with hydraulic separator fan coil ...
Страница 123: ...27 NOTE ...
Страница 124: ...28 ...
Страница 125: ......
Страница 126: ......