22
ICE CFA1012A I&O Manual 01/2021 New
Chapter 4 Troubleshooting
4.1 Overview
WARNING
Failure to follow these instructions could result in death, severe personnel injury
and/or property damage.
A comprehensive understanding of the operation of the CFA1012A is a prerequisite to troubleshooting.
Please read the Chapter 1 for basic information about the unit.
ICE CFA1012As are thoroughly tested before they are shipped from the factory. Or course, it is possible
that a defect may escape undetected, or damage may have occurred during transportation. However,
the great majority of problems result from installation errors.
If you experience difficulties with the CFA1012A, please review the installation steps in Chapter 2. It
may be helpful to get another person to review and check them with you.
Much time can be saved by taking a thoughtful and orderly approach to troubleshooting. Start with a
visual check - are there loose wires, crimped tubing, missing parts, etc? Begin deeper analysis only
after making this initial inspection.
The troubleshooting information in this manual is basic. The troubleshooting section contains problem/
solution charts for general problems, followed by a compressor section.
Not every problem can be anticipated. If you discover a problem that is not covered in this manual, we
would be very grateful if you would bring it to the attention of our service department for incorporation
in future revisions.
As always, please exercise caution and good judgement when servicing the CFA1012A. Use only safe
and proven service techniques. Use refrigeration goggles when servicing the refrigeration circuit.
The refrigerant circuit has hot surfaces, and the electrical voltages inside of the unit may be hazardous
or lethal.
SERVICE MAY BE PERFORMED ONLY BY QUALIFIED AND EXPERIENCED PERSONS.
4.2 Failure Symptoms Guide
PROBLEM/SYMPTOM
LIKELY CAUSE(S)
CORRECTION
A. Unit does not run.
NOTE: An internal anti-short-cycle
timer will prevent the unit
from starting for .2 to 8
minutes following start-up.
1. Power supply problem.
2. Tripped internal disconnect.
3. Shut off by external thermostat or
thermostat is defective.
4. Unit off on high or low pressure limit.
5. Internal component or connection
failure.
1. Check power supply for adequate phase and voltage.
Check wiring to unit and external breakers or fuses.
2. Check internal circuit protection devices for continuity.
3. Check operation of wall-mounted thermostat.
4. Reset pressure switch.
5. Check for loose wiring. Check components for failure.