ICE CFA1012A I&O Manual 01/2021 New

1.7  Electronic Control Board Mode of Operation

Normal

24 VAC power must be continuously applied to “R” and “C”. Upon a call for cooling “Y” and with the 

high pressure switch (HPS) closed, the compressor will be energized. (Note: See the delay on make 

feature.)  The compressor will remain energized during the 3 minute timed low pressure by-pass cycle. If 

the low pressure switch (LPS) is open after the 3 minute by-pass cycle, the compressor will de-energize. 

Lock-out

If either of the fault conditions (LPS or HPS) occurs twice during the same call for cooling, the control 

board will enter into and indicate the lockout mode. In the lockout mode, the compressor is turned off. 

If there is a call for indoor air flow “G”, the blower remains energized, the alarm output is energized and 

the status LED will blink to indicate which fault has occurred. When the lockout condition is cleared, the 

unit will reset if the demand for the thermostat is removed or when the power is reset. With the control 

board, the user can now have either normally closed or normally open remote alarm dry contacts. The 

air conditioners are factory wired to be normally open. 

Delay on Break

If the compressor is de-energized due to a loss of a cooling “Y” call or the first fault, the unit re-start 

will be delayed 3 minutes from the time the contactor is de-energized.  (Note: There is no delay on 

break if the lockout condition is reset.)

Delay on Make

On initial power up only, the unit will wait 0.03 to 10 minutes from the cooling “Y” call before al-

lowing the contactor to energize. The delay can be adjusted by the DOM wheel on the board. Factory 

recommended wait is 3 minutes.

Low Pressure By-Pass Time

When starting, the low pressure switch (LPS) fault condition will be by-passed for 3 minutes before 

the contactor is de-energized.

Post Purge

Upon a call for indoor airflow “G” the blower will energize immediately.  When in the cooling mode, 

the blower will remain energized for 10 to 90 seconds (adjustable) after the compressor has been de-

energized. The time period can be changed by fan purge wheel on the board. Factory setting is 90 seconds.

LED Indicator Lights

COLOR

TYPE

STATUS

DESCRIPTION

Green

Power

Contstant On

24 VAC power has been applied

Red

Status

Contstant On

Normal operation

Red

Status

1 Blink

High pressure switch has opened twice

Red

Status

2 Blinks

Low pressure switch has opened twice

Low Ambient Control

The low ambient control permits cooling when outdoor ambient temperatures are low. The control uses 

a reverse-acting high pressure switch to cycle the condenser fan motor according to liquid refrigerant 

pressure conditions. Switch closure and fan operation occurs when the pressure reaches 400 PSIG. The 

switch opens again when the refrigerant pressure falls to 245 PSIG. Therefore, the outdoor fan always 

starts after the compressor, and 

it will cycle frequently during normal operation at low outdoor 

conditions.

Содержание Industrial Climate Engineering CFA1012A

Страница 1: ...oded View Parts List 26 Installation Operation Manual Vertical Air Conditioners Model CFA1012A Manufactured By Industrial Climate Engineering Division of AIRXCEL Inc P O Box 5104 Cordele Georgia 31010...

Страница 2: ...UNIT UPRIGHT Laying it down on its side may cause oil to leave the compressor and breakage or damage to other components 3 TURN ELECTRICAL POWER OFF AT THE breaker or fuse box BEFORE installing or wor...

Страница 3: ...thermostat END USER Retain these instructions for future reference Table of Contents Chapter 1 Air Conditioner Description Specifications 1 1 General Description 5 1 2 Model Identification 5 1 3 Seri...

Страница 4: ...e 3 Control Board Detail 11 Figure 4 Wall Mount Detail 15 Figure 5 Thermostat Wiring Diagram 17 Tables Table 1 Summary Ratings 6 Table 2 Electrical Characteristics 6 Table 3 Unit Load Amps 6 Table 4 A...

Страница 5: ...ing plate located on side panel Example C F A 1 0 1 2 A A 0 3 6 A 1 3 D A A 1 1 Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 1 Unit Designation Family C In...

Страница 6: ...ry Coil Model 00 05 10 15 20 25 CFA1012A 510 470 450 420 390 360 CFM Cubic Feet Minute Indoor Air Flow ESP External Static Pressure in Inches WG Note Follow local codes and standards when designing du...

Страница 7: ...3 4 197 mm 15 1 2 394 mm BACK OF UNIT ECUA12 SLIMPAC 1 1 2 38 mm 15 381 mm 1 5 8 41 mm 1 7 8 48 mm 1 7 8 48 mm 14 3 8 365 mm 57 7 8 1470 mm 11 3 4 298 mm 56 3 8 1432 mm 19 1 4 489 mm 2 3 8 60 mm 8 5...

Страница 8: ...s to liquid as heat is transferred to outdoor air drawn across the condenser by the condenser fan Liquid refrigerant is expanded into the evaporator through the metering device to repeat the cycle Coo...

Страница 9: ...9 ICE CFA1012A I O Manual 01 2021 New 1 6 Electrical Diagrams Figure 2 Typical Electrical Schematic...

Страница 10: ...gized Note There is no delay on break if the lockout condition is reset Delay on Make On initial power up only the unit will wait 0 03 to 10 minutes from the cooling Y call before al lowing the contac...

Страница 11: ...G the system must be manually reset once the lockout circuit is activated A manual reset is necessary to prevent harmful short cycling To reset switch turn primary power off then back on or turn therm...

Страница 12: ...p return the unit to the freight carrier 2 2 Installation Requirements General 1 Inspect unit for completeness Check for missing parts e g hardware Refer to the installation kit information in section...

Страница 13: ...package may include other factory supplied items optional as follows PART DESCRIPTION 50123 Digital thermostat 1 stage heat 1 stage cool 7 day programmable Fan switch Auto On Auto change over Keypad l...

Страница 14: ...sons could result in hazards to you and others Installation MUST conform with local codes or in the absence of local codes with codes of all governmental authorities have jurisdiction The information...

Страница 15: ...Use fabric boots to prevent the transmission of vibration through the duct system The fabric must be U L rated UL 181 to a minimum of 197 F 2 6 Bottom Bracket Installation Wall Openings Measure the di...

Страница 16: ...fore connecting line voltage Important All electrical work must meet the requirements of local codes and ordinances Work should be done only by qualified persons The CFA1012A units are provided with l...

Страница 17: ...17 ICE CFA1012A I O Manual 01 2021 New CFA1012A 20 A Figure 5 Thermostat Wiring Diagram...

Страница 18: ...________ Compressor Model No ______________________________________________ Serial No ______________________________________________ B Pre Start Up Is there any shipping damage Yes No If so where ____...

Страница 19: ...voltage ______________volts Voltage imbalance 100 x Max Deviation avg Voltage ___________ A voltage deviation greater than 2 with the unit running should be addressed and corrected Excess voltage devi...

Страница 20: ...________ Evap Leaving Air WB Temp ________ ________ Heater Contactor Amps L1 ________ ________ Heater Contactor Amps L2 ________ ________ Heater Contactor Amps L3 ________ ________ E Cooling Mode Chec...

Страница 21: ...3 ________ ________ Notes _________________________________________________________________________ _________________________________________________________________________ __________________________...

Страница 22: ...general problems followed by a compressor section Not every problem can be anticipated If you discover a problem that is not covered in this manual we would be very grateful if you would bring it to t...

Страница 23: ...oper connection in field wiring 3 Internal short circuit Loose or improper connection s in unit 4 Excessively high or low supply volt age or phase loss 3 only 1 Note electrical requirements in Chapter...

Страница 24: ...y be open You may have to wait several hours for it to reset 3 Motor Winding Resistances Using a digital volt ohm meter VOM measure the resistance across the compressor windings as shown below C S R R...

Страница 25: ...ot to wet any of the electrical components Be sure the unit has dried before restarting Condenser Periodicallyinspecttheoutdoorcondensercoilandthecabinetairreliefsfordirtorobstructions Remove foreign...

Страница 26: ...other material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by operating or staging the unit in a corrosive environment 4 Damages ca...

Отзывы: