6
Eubank 7AA1024A-1060A & 7AA2036A-2060A I&O Manual
07/2021 Rev.3
MODEL
0.10
0.15
0.20
0.25
0.30
0.40
0.50
7AA1024A
800
785
770
725
680
600
500
7AA1030A
1200
1150
1100
1050
1000
900
800
7AA1036A
1290
1230
1170
1115
1060
1000
920
7AA1042A
1500
1430
1360
1295
1230
1160
1070
7AA1048A
1900
1850
1800
1700
1600
1500
1350
7AA1060A
1900
1850
1800
1700
1600
1500
1350
7AA2036A
1290
1230
1170
1115
1060
1000
920
7AA2042A
1500
1430
1360
1295
1230
1160
1070
7AA2048A
1900
1850
1800
1700
1600
1500
1350
7AA2060A
1900
1850
1800
1700
1600
1500
1350
Values in bold are the minimum air flow.
Air flow ratings of 208-230 volt units are at 230v. Air flow ratings of 460 volt units are at 460 volts. Operation of units at a voltage different from
the rating point will affect air flow
.
Table 3. CFM @ External Static Pressure (Wet Coil) (IWG)
MODEL
LBS
KG
Non-Economizer
7AA1024A
395
179
7AA1030A/1036A & 7AA2036A/2042A
451
205
7AA1048A/1060A & 7AA2048A/2060A
599
272
With Economizer
7AA1024A
415
188
7AA1030A/1036A & 7AA2036A/2042A
471
214
7AA1048A/1060A & 7AA2048A/2060A
619
281
Table 4. Shipping Weights for Eubank Wall Mount AC Units