the heater element. This includes proper supply duct sizing, sufficient quantity of supply registers,
and adequate return and filter areas. Duct work must be of correct material and must be properly
insulated. Duct work must be constructed of galvanized steel with a minimum thickness of .019
inches. Duct work must be firmly attached, secured, and sealed to prevent air leakage. See section
2.4 for additional duct work requirements.
5.
Clearances:
Note the minimum clearances required for proper operation and service.
MODEL
MIN. CLEARANCE
AROUND
SIDES (SINGLE UNIT)
MIN. CLEARANCE
BETWEEN
UNITS (TWO UNITS)
MIN. SPACE
ABOVE UNIT
MIN. SPACE
BELOW UNIT
A
B
C
D
1024A
30 inches (76 cm)
18 inches (46 cm)
24 inches (61 cm)
6 inches (15 cm)
1030A/1036A &
2030A/2036A
30 inches (76 cm)
18 inches (46 cm)
24 inches (61 cm)
6 inches (15 cm)
1042A/1048A/1060A &
2042A/2048A/2060A
30 inches (76 cm)
30 inches (76 cm)
24 inches (61 cm)
6 inches (15 cm)
Table 8 Minimum Clearances
6.
Codes:
Make sure your installation conforms to all applicable electrical, plumbing, building, and municipal
codes. Some codes may limit installation to single story structures.
7.
Electrical Supply:
The power supply must have the appropriate voltage, phase, and ampacity for the model selected.
Voltage must be maintained above minimum specified values listed below. Refer to the data sticker
on the unit for ampacity requirements.
Electrical Rating Designations*
A
C
D
Nominal Voltage
208/230
208/230
460
Phase
1
3
3
Minimum Voltage
197
197
414
Maximum Voltage
253
253
506
* Letters refer to model number code designations. Refer to page 5.
Table 9 Voltage Limitations