INSTALLATION, OPERATION AND 

MAINTENANCE INSTRUCTIONS

FOR 45000 SERIES HEAT PUMPS

P/N: 1980-054 

04-26-2016

RV Products Division

These instructions are a general guide for installing the 45000 Series Coleman-Mach roof top Heat Pumps.  For 

specific Heat Pump details, it will be necessary to refer to ALL printed documents supplied with this unit.

IMPORTANT NOTICE

These instructions are for the use of qualified individuals specially trained and experienced in installation of this type 

equipment and related system components.
Installation and service personnel are required by some states to be licensed.  PERSONS NOT QUALIFIED SHALL 

NOT INSTALL NOR SERVICE THIS EQUIPMENT.

NOTE:

    The  words  “Shall”  or  “Must”  indicate  a  requirement  which  is  essential  to  satisfactory  and  safe  product 

performance.  The words “Should” or “May” indicate a recommendation or advice which is not essential and not 

required but which may be useful or helpful.

WARNING! – SHOCK HAZARD 

To prevent the possibility of severe personal injury or equipment damage due 

to electrical shock, always be sure the electrical power source to the appliance is disconnected.

CAREFULLY FOLLOW ALL INSTRUCTIONS AND WARNINGS IN THIS BOOKLET TO

AVOID DAMAGE TO THE EQUIPMENT, PERSONAL INJURY OR FIRE.

WARNING!

  Improper installation may damage equipment, can create a hazard and will void the warranty.

The use of components not tested in accordance with these units will void the warranty, may make the equipment 

in violation of state codes, may create a hazard and may ruin the equipment.

TABLE OF CONTENTS

I.

General Information

2

II.

Heat Pump Sizing

2

III.

Selecting an Installation Location

2

IV.

Installing the Roof Top Unit

2

A.

Standard Installation

2

B.

OEM Top/Down Mounting

4

V.

Electrical Wiring

4

VI.

Installing Optional Heater Accessory

6

VII.

Installing Ceiling Assembly 

(9600 Series)

6

VIII.

System Checkout

6

IX.

Operation and Maintenance

10

i.

General Information

10

ii.

Control Panel

10

iii.

Operation

11

iv.

Maintenance

11

v.

Wall Thermostat Identification and Operation

12

vi.

Warranty Service

12

X.

Optional Extended Warranty

28

Содержание 45000 Series

Страница 1: ...CK HAZARD To prevent the possibility of severe personal injury or equipment damage due to electrical shock always be sure the electrical power source to the appliance is disconnected CAREFULLY FOLLOW...

Страница 2: ...eat Pump will not operate III SELECTING AN INSTALLATION LOCATION Your Airxcel Inc Heat Pump has been designed for use primarily in recreational vehicles Is the roof of the vehicle capable of supportin...

Страница 3: ...ounted as near level from front to rear and side to side as is possible when the vehicle is parked on a level plane Figure 3 shows maximum allowable degree deviations mounting degrees from total surfa...

Страница 4: ...fs may require additional support gaskets provided by the OEM Tighten the front screws until the unit gasket has been evenly compressed Use care to NOT STRIP the screws See Figure 5 and 6 5 Apply sili...

Страница 5: ...IS AVAILABLE AT www AIRXCEL com IT IS THE RESPONSIBILITY OF THE INSTALLER TO PROVIDE THE MEANS FOR SEGREGATION OF SUPPLY AND RETURN AIR 1 08 16 15 1 98 16 94 47 13 06 REAR BASE PADS DIMENSIONS FROM 14...

Страница 6: ...y from carton separate individual items and remove the two grilles and filters from the ceiling shroud B Fasten the duct collar to the Heat Pump basepan with 3 provided screws See Figure 11 C Raise th...

Страница 7: ...FIGURE 9 FIGURE 10 7...

Страница 8: ...8 ROOFTOP UNIT ROOF STRUCTURE MOUNTING FRAME DUCT COLLAR CEILING ASSEMBLY CHUTE FABRIC DUCT MATERIAL CEILING ASSEMBLY SHROUD CONTROL KNOBS GRILLES FILTERS FIGURE 11...

Страница 9: ...andard warranty knowing you have protection for an additional three 3 years should you experience part failure excluding shrouds filters and complete Heat Pumps on your Coleman Mach Heat Pump Free rep...

Страница 10: ...n a shaded area keeping windows and doors shut and avoiding the use of heat producing appliances in the vehicle will help to reduce the heat gain When possible the addition of insulation and tinted gl...

Страница 11: ...e air is to flow Discharge air temperature can be controlled to some extent by opening or closing the louvers When the louvers are closed the warmest localized discharge air is achieved Fully opened l...

Страница 12: ...developing cracks or has suffered damage from impact v WALL THERMOSTAT IDENTIFICATION AND OPERATION If your Coleman Mach roof top unit is controlled by a wall thermostat refer to the operation manual...

Страница 13: ...13 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 14: ...sp cialement form et exp riment dans l installation de ce type d quipement et des l ments s y rattachant Dans certains tats on exige que le personnel d installation et d entretien d tienne une licence...

Страница 15: ...de chaleur lev songez une meilleure isolation du v hicule installer des auvents au dessus des fen tres ou les faire teinter III S LECTION DE L EMPLACEMENT D INSTALLATION Votre pompe a chaleur Airxcel...

Страница 16: ...e doit permettre le passage du c blage d alimentation Acheminez le c blage d alimentation dans le cadre au moment de son installation IMPORTANT Pr voyez 61 cm 24 po de c blage d alimentation travers l...

Страница 17: ...tallation 4 l aide de 4 vis de fixation et les rondelles d tanch it ex cutez les vis travers les trous de la bride 2 de cloison 2 avant des supports de montage et dans le toit du v hicule Serrer les v...

Страница 18: ...IS AVAILABLE AT www AIRXCEL com IT IS THE RESPONSIBILITY OF THE INSTALLER TO PROVIDE THE MEANS FOR SEGREGATION OF SUPPLY AND RETURN AIR 1 08 16 15 1 98 16 94 47 13 06 REAR BASE PADS DIMENSIONS FROM 14...

Страница 19: ...S RIE 9600 Confirmez que vous avez correctement appari la pompe chaleur de toit et l ensemble de plafond Vous devez ex cuter les instructions pas pas dans l ordre qui suit afin d assurer une installa...

Страница 20: ...FIGURE 9 FIGURE 10 20...

Страница 21: ...ROOFTOP UNIT ROOF STRUCTURE MOUNTING FRAME DUCT COLLAR CEILING ASSEMBLY CHUTE FABRIC DUCT MATERIAL CEILING ASSEMBLY SHROUD CONTROL KNOBS GRILLES FILTERS FIGURE 11 21...

Страница 22: ...un trois 3 ans si vous rencontrez d faillance d une pi ce suppl mentaire l exclusion des linceuls des filtres et des pompe a chaleurs complets sur votre air Coleman Mach conditionneur Pi ces de recha...

Страница 23: ...23 CETTE PAGE EST INTENTIONNELLEMENT BLANK...

Страница 24: ...t et des verres teint s tout particuli rement dans les caravans non isol es IX MODE D EMPLOI ET UTILISATION S RIES 45000 DES CLIMATISEURS DE TOIT DES PL NUM DE PLAFOND REMARQUE Le montage de chauffage...

Страница 25: ...chaleur diminue de quelques degr s sous le r glage choisi Lorsque la temp rature de l air qui entre dans le pompe a chaleur augmente au dessus de ce r glage il arr tera le compresseur Le chauffage con...

Страница 26: ...rait aussi utile de faire un examen du couvercle de plastique couvrant le pompe a chaleur sur le toit S assurer que les quatre vis de montage et les rondelles sont bien en place et retiennent le couve...

Страница 27: ...27 CETTE PAGE EST INTENTIONNELLEMENT BLANK...

Страница 28: ...illing out the application below and mailing it with your check or money order for 89 95 to Airxcel Inc P O Box 4020 Wichita KS 67204 A contract will be sent to you within a few weeks You should retai...

Отзывы: