background image

11

iii.  OPERATION

I.  For Cooling (Refer to Figure 1, page 9).

A.

  Turn  the  selector  switch  to  the  “LOW  COOL”  or 

“HIGH COOL” position.

B.

  Rotate  the  thermostat  (temperature  control)  to  the 

position  that  is  the  most  comfortable  to  you.    The 

thermostat  will  turn  the  compressor  on  when  the 

temperature of the air entering the Heat Pump rises 

a few degrees above the setting you have selected.  

Then the temperature of the air entering continues 

to  cycle  the  compressor  on  and  off  in  the  above 

mentioned fashion until the selector switch is turned 

to another mode of operation.

C.

  Position  the  louvers  to  the  desired  direction  the 

discharge air is to flow.

 

Note:

  The fan operation is constant, only the compressor 

cycles on the thermostat.

II.   Operation During Cooler Nights 

(Cooling Operation).

It is important, when the outdoor temperature drops in 

the evening or during the night to below 75 degrees F., 

that  the  thermostat  (temperature  control)  be  set  at  a 

midpoint between “Warmer” and “Cooler”.  If the setting 

is at “Cooler”, the evaporator coil may become iced-up 

and stop cooling.  During the day when the temperatures 

have  risen  above  75  degrees  F.,  reset  the  thermostat 

switch to the desired setting.

NOTE:

  Should icing-up occur, it is necessary to let the cooling 

(evaporator)  coil  defrost  before  normal  cooling  operation  is 

resumed.  During this time, operate the unit in the “HIGH FAN” 

position with the system at maximum air flow.  When increased 

or full air flow is observed, the cooling coil should be clear of ice.

III.  Short Cycling

When  an  Heat  Pump  is  in  operation,  its  compressor 

circulates refrigerant under high pressure.  Once off, it will 

take two to three minutes for this high pressure to equalize.

The  Heat  Pump  compressor  is  unable  to  start  against 

high pressure.  Therefore, once the Heat Pump is turned 

off, it is important to leave it off for two to three minutes 

before restarting.

Short  cycling  the  compressor  (or  starting  it  before 

pressures have equalized), will in some instances, kick 

the circuit breaker or overload.

IV. For Heating (“Elect-A-Heat” Ceiling Assembly 

Model Only) Refer to Figure 1, page 9).

The optional Elect-A-Heat heating assembly is intended 

to take the chill out of the indoor air when the air is a few 

degrees too cool for comfort.  The heating assembly is an 

effective “chill chaser”.  It is not a substitute for a furnace.

Do not expect the heating coil on your heater to glow.  

Because the fan draws in cold air and forces it over the 

coil, the coil will not turn red.  A hint of red may occur 

where the moving air does not directly touch the coil.

A.

  Turn the selector switch to the “LOW HEAT” position.  

At “LOW HEAT”, the fan operates on low speed with 

heat output at maximum.

B.

  Rotate the thermostat (temperature control) switch 

to  the  position  that  is  the  most  comfortable  to 

you.    The  thermostat  will  turn  the  heater  on  when 

the temperature of the air entering the Heat Pump 

unit  drops  below  this  setting  a  few  degrees  and 

automatically  turns  off  when  the  temperature  of 

the air entering the Heat Pump rises a few degrees 

above this setting.  The heater will continue to cycle 

on and off in this fashion until the selector switch is 

turned to another mode of operation.

C.

  Position  the  louvers  to  the  desired  direction  the 

discharge air is to flow.

 

Discharge air temperature can be controlled to some 

extent by opening or closing the louvers.

 

When  the  louvers  are  closed,  the  warmest  localized 

discharge  air  is  achieved.    Fully  opened  louvers  will 

throw the warm discharge air to the back and front of the 

vehicle for more efficient circulation and faster warm-up.  

Although the air temperature is lower with the louvers 

fully opened, the heating capacity is still the same.

V.  For Air Circulation Only 

(Refer to Figure 1, page 9).

A.

  Turn  the  selector  switch  to    “LOW  FAN”  or  for 

maximum air flow, to “HIGH FAN”.

B.

  Position  the  louvers  to  the  desired  direction  the 

discharge air is to flow.

NOTE:

  When the selector switch is in the “LOW FAN” or “HIGH 

FAN” position, the blower motor will operate continuously.

iv.  MAINTENANCE

I.   Owner

  -  One  of  the  biggest  advantages  to  your  new 

Coleman-Mach Heat Pump is that the maintenance 

needed to keep the unit in good working order is minimal.  

In fact about the only thing you, the owner, must take care 

of is the cleaning and replacement of the filters.

Filters are made from long life non-allergenic natural 

fibers  which  can  be  cleaned  and  reused,  and  which 

completely filter the circulated air when the Heat Pump 

is in operation.  If the filters are not cleaned at regular 

intervals,  they  may  become  partially  clogged  with  lint, 

dirt, grease, etc.  A clogged filter will produce a loss of 

air volume and may eventually cause an icing-up of the 

cooling (evaporator) coil.

IMPORTANT

Do not operate your Heat Pump for extended periods 

of time without the filter installed.

An even more serious condition occurs when the Heat 

Pump is operated without a filter.  When this happens 

the lint, grease, etc. that are normally stopped by the 

filter are now accumulating in the cooling coil.  This not 

only leads to a loss of air volume and a possible icing-

up of the cooling coil, but could also result in serious 

damage to the operating components of the Heat 

Pump.

We recommend that the filters be cleaned and changed at 

least every two weeks when the Heat Pump is in operation.

Cleaning and/or changing the filters:

1. 

Remove the two grilles from the ceiling assembly by 

pulling the tabs on the grilles.

2. 

Remove and clean or replace the two filters.

3. 

Re-install  the  filters  and  grilles  in  the  ceiling 

assembly as shown in Figure 2.

4. 

If the vehicle is equipped with  a flush mount ceiling 

assembly, remove the four return air grille screws. 

Remove  filter  from  the  grille  and  either  clean  or 

exchange with new filters.

NOTE:

    If  replacement  filters  are  necessary,  the  filters  can  be 

purchased from most Airxcel, Inc. Authorized Service Centers.  It 

is  recommended  that  spare  filters  be  carried  with  the  RV  at  all 
times to replace worn, torn or deteriorated filters.

II.  Service Person

A.

  Electrical  –  All  electrical  work  and/or  inspection 

should  be  performed  only  by  qualified  service 

personnel.    Contact  your  nearest  Airxcel,  Inc. 

Service Center if electrical problems should arise.

B.

  Check Points – Failure to start or to cool the air are 

sometimes  problems  with  Heat  Pump  units.    The 

Coleman-Mach RV Heat Pump is designed to operate 

on 115 volt electrical power.  If the compressor on the 

Heat Pump fails to start, check with your Airxcel, Inc. 

Service Center to determine that the proper wire size 

is connected to the unit, the proper circuit breakers are 

installed as protection devices on the electrical circuit 

and the proper sized extension cord is being used for 

Содержание 45000 Series

Страница 1: ...CK HAZARD To prevent the possibility of severe personal injury or equipment damage due to electrical shock always be sure the electrical power source to the appliance is disconnected CAREFULLY FOLLOW...

Страница 2: ...eat Pump will not operate III SELECTING AN INSTALLATION LOCATION Your Airxcel Inc Heat Pump has been designed for use primarily in recreational vehicles Is the roof of the vehicle capable of supportin...

Страница 3: ...ounted as near level from front to rear and side to side as is possible when the vehicle is parked on a level plane Figure 3 shows maximum allowable degree deviations mounting degrees from total surfa...

Страница 4: ...fs may require additional support gaskets provided by the OEM Tighten the front screws until the unit gasket has been evenly compressed Use care to NOT STRIP the screws See Figure 5 and 6 5 Apply sili...

Страница 5: ...IS AVAILABLE AT www AIRXCEL com IT IS THE RESPONSIBILITY OF THE INSTALLER TO PROVIDE THE MEANS FOR SEGREGATION OF SUPPLY AND RETURN AIR 1 08 16 15 1 98 16 94 47 13 06 REAR BASE PADS DIMENSIONS FROM 14...

Страница 6: ...y from carton separate individual items and remove the two grilles and filters from the ceiling shroud B Fasten the duct collar to the Heat Pump basepan with 3 provided screws See Figure 11 C Raise th...

Страница 7: ...FIGURE 9 FIGURE 10 7...

Страница 8: ...8 ROOFTOP UNIT ROOF STRUCTURE MOUNTING FRAME DUCT COLLAR CEILING ASSEMBLY CHUTE FABRIC DUCT MATERIAL CEILING ASSEMBLY SHROUD CONTROL KNOBS GRILLES FILTERS FIGURE 11...

Страница 9: ...andard warranty knowing you have protection for an additional three 3 years should you experience part failure excluding shrouds filters and complete Heat Pumps on your Coleman Mach Heat Pump Free rep...

Страница 10: ...n a shaded area keeping windows and doors shut and avoiding the use of heat producing appliances in the vehicle will help to reduce the heat gain When possible the addition of insulation and tinted gl...

Страница 11: ...e air is to flow Discharge air temperature can be controlled to some extent by opening or closing the louvers When the louvers are closed the warmest localized discharge air is achieved Fully opened l...

Страница 12: ...developing cracks or has suffered damage from impact v WALL THERMOSTAT IDENTIFICATION AND OPERATION If your Coleman Mach roof top unit is controlled by a wall thermostat refer to the operation manual...

Страница 13: ...13 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 14: ...sp cialement form et exp riment dans l installation de ce type d quipement et des l ments s y rattachant Dans certains tats on exige que le personnel d installation et d entretien d tienne une licence...

Страница 15: ...de chaleur lev songez une meilleure isolation du v hicule installer des auvents au dessus des fen tres ou les faire teinter III S LECTION DE L EMPLACEMENT D INSTALLATION Votre pompe a chaleur Airxcel...

Страница 16: ...e doit permettre le passage du c blage d alimentation Acheminez le c blage d alimentation dans le cadre au moment de son installation IMPORTANT Pr voyez 61 cm 24 po de c blage d alimentation travers l...

Страница 17: ...tallation 4 l aide de 4 vis de fixation et les rondelles d tanch it ex cutez les vis travers les trous de la bride 2 de cloison 2 avant des supports de montage et dans le toit du v hicule Serrer les v...

Страница 18: ...IS AVAILABLE AT www AIRXCEL com IT IS THE RESPONSIBILITY OF THE INSTALLER TO PROVIDE THE MEANS FOR SEGREGATION OF SUPPLY AND RETURN AIR 1 08 16 15 1 98 16 94 47 13 06 REAR BASE PADS DIMENSIONS FROM 14...

Страница 19: ...S RIE 9600 Confirmez que vous avez correctement appari la pompe chaleur de toit et l ensemble de plafond Vous devez ex cuter les instructions pas pas dans l ordre qui suit afin d assurer une installa...

Страница 20: ...FIGURE 9 FIGURE 10 20...

Страница 21: ...ROOFTOP UNIT ROOF STRUCTURE MOUNTING FRAME DUCT COLLAR CEILING ASSEMBLY CHUTE FABRIC DUCT MATERIAL CEILING ASSEMBLY SHROUD CONTROL KNOBS GRILLES FILTERS FIGURE 11 21...

Страница 22: ...un trois 3 ans si vous rencontrez d faillance d une pi ce suppl mentaire l exclusion des linceuls des filtres et des pompe a chaleurs complets sur votre air Coleman Mach conditionneur Pi ces de recha...

Страница 23: ...23 CETTE PAGE EST INTENTIONNELLEMENT BLANK...

Страница 24: ...t et des verres teint s tout particuli rement dans les caravans non isol es IX MODE D EMPLOI ET UTILISATION S RIES 45000 DES CLIMATISEURS DE TOIT DES PL NUM DE PLAFOND REMARQUE Le montage de chauffage...

Страница 25: ...chaleur diminue de quelques degr s sous le r glage choisi Lorsque la temp rature de l air qui entre dans le pompe a chaleur augmente au dessus de ce r glage il arr tera le compresseur Le chauffage con...

Страница 26: ...rait aussi utile de faire un examen du couvercle de plastique couvrant le pompe a chaleur sur le toit S assurer que les quatre vis de montage et les rondelles sont bien en place et retiennent le couve...

Страница 27: ...27 CETTE PAGE EST INTENTIONNELLEMENT BLANK...

Страница 28: ...illing out the application below and mailing it with your check or money order for 89 95 to Airxcel Inc P O Box 4020 Wichita KS 67204 A contract will be sent to you within a few weeks You should retai...

Отзывы: