CONTROL SYSTEM

11-3

SM FSF045 1-A.0 GB

11.8.3 

Low Pressure Protection of Compressor by low pressure switch

• 

Comp is on, 

After the compressor has run for 2 minutes, the unit will begin to detect the signal of low pressure 
switch, If it is detected within 60 seconds continuously that the low-pressure switch is cut off, the unit 
will stop, 3 min later, if the protection is gotten over, the unit will resume operation automatically. Or 
else, the fault (E3)will display and  the unit can not resume operation automatically. it can resume by 
pressing ON/OFF.

• 

Comp is off

if it’s detected that the low pressure switch is cut off for 30s continuously, the unit will stop running. 
Meanwhile, E3 will be displayed and the unit can’t resume running automatically. Only after restarting 
up the unit and the low pressure switch is resumed, the unit can resume running.

11.8.4 

Compressor over Heating Protection

After the compressor is started up, if it

s detected that the discharge temperature is too high for 30s 

successively, the unit will stop running,  When compressor has stopped for 3mins and discharge 
temperature resumes to normal range CTT<90

, the unit will resume running.

If above protection is occurred for twice successively, the complete unit can

t resume running and E4 

will be displayed. When restarting up the unit and CTT<90

, the unit will run at setting mode.

If turning on the unit to turn to heating mode or switching to heating mode from other modes, discharge 
protection will be shielded for 1min when compressor is started up for the first time.

11.8.5 

Compressor over Current Protection

After compressor is started up, if it’s detected that the current is exceeds I0 (I0=25A) for 3s 
successively, the unit will stop running After compressor has stopped for 3mins, the unit will resume 
original running status. If protection times exceeds 6 times, indicator will blink and display E5 and the 
unit can’t resume original running status. 
The unit can only resume running after restarting up the unit.

11.8.6 

Outdoor Coil Deicing Protection

This protection is for Heat Pump Only
This protection is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat 
exchanger temperature must be more than its setting values when finishing the deicing protection.
In the deicing protection, IFAN is forced OFF.

Deicing Starting Conditions

The starting conditions must be made with the outdoor air temperature (OAT) and outdoor coil 
temperature (OCT). Under the conditions that the system is in heating operation for certain period 
(Accumulated time) 

Deicing process

H1 will be displayed during deicing. If there’s auxiliary heating, auxiliary heating will be stopped and 
then compressor, indoor fan and outdoor fan will stop running after 1min delayed. 3mins later, the 
four-way valve will be OFF. After four-way valve is OFF for 30s, compressor will be started up.After 
deicing is finished, compressor will stop running, while the four-way valve will be ON. 30s later, 
compressor and outdoor fan will be restarted up. Indoor fan is running at anti cold air status. 
The max Deicing Time is 12 minutes. 

11.8.7 

Overheating protection in heating mode

In heating mode, when it’s detected that the evaporator tube temperature (ICT) is too high, outdoor 
fan will stop running; when evaporator  tube temperature resumes to normal range, outdoor fan will 
be started up.

Содержание YFF045

Страница 1: ...YFF Series Indoor Units Outdoor Units FSF045 YFF045 DECEMBER 2010 REFRIGERANT HEAT PUMP R410A SM FSF045 1 A 0 GB...

Страница 2: ...sue for original and changed pages are Original 0 March 2009 Total number of pages in this publication is 53 consisting of the following Page No Revision No Page No Revision No Page No Revision No Tit...

Страница 3: ...ONS 3 1 4 OUTLINE DIMENSIONS 4 1 5 PERFORMANCE DATA PRESSURE CURVES 5 1 6 SOUND LEVEL CHARACTERISTICS 6 1 7 WIRING DIAGRAMS 7 1 8 ELECTRICAL DATA 8 1 9 REFRIGERATION DIAGRAMS 9 1 10 TUBING CONNECTIONS...

Страница 4: ...lure Cold air prevention in heating Self diagnostic Error indications for ease of maintenance LED display Crank heater Optional 1 3 Indoor Unit The indoor unit is floor stanging and can be easily fitt...

Страница 5: ...t Data Sheet Chapter 2 It includes Compressor mounted in a soundproofed compartment Axial fan Outdoor coil with hydrophilic louver fins for RC units Outlet air fan grill Service valves flare type conn...

Страница 6: ...D mm 2080 735 530 9 8 g k t h g i e w d e g a k c a P s t i n u t e l l a p r e p s t i n U s t i n u t h g i e h g n i k c a t S OUTDOOR y r a l l i p a C l o r t n o c t n a r e g i r f e R A 8 3 H...

Страница 7: ...nd EN 14511 Cooling Indoor 27o C DB 19o C WB Outdoor 35 o C DB Heating Indoor 20o C DB Outdoor 7o C DB 6o C WB 3 1 Operating Limits R410A Indoor Outdoor Cooling Upper limit 32o C DB 23o C WB 43o C DB...

Страница 8: ...OUTLINE DIMENSIONS 4 1 SM FSF045 1 A 0 GB 4 OUTLINE DIMENSIONS 4 1 Indoor Unit FSF045 4 2 Outdoor Unit YFF045 Model W H D FSF045 518 1870 395...

Страница 9: ...Data ENTERING AIR WB DB ID Coil o C 15 21 17 24 19 27 21 29 23 32 15 1 TC SC PI 20 1 TC SC PI 25 TC SC PI 30 TC SC PI 35 TC SC PI 40 TC SC PI 46 TC SC PI LEGEND TC Total Cooling Capacity kW SC Sensibl...

Страница 10: ...o C TH Pl TH Pl TH Pl 10 7 2 2 6 10 15 20 LEGEND TH Total Heating Capacity kW PI Power Input kW WB Wet Bulb Temp o C DB Dry Bulb Temp o C ID Indoor OD Outdoor 5 1 3 Capacity Correction Factor Due to T...

Страница 11: ...PERFORMANCE DATA PRESSURE CURVES 5 3 SM FSF045 1 A 0 GB T O B E C O M P L E T E D 5 4 Pressure Curves SAF024 OU7 24 Z R410A 5 4 1 Cooling...

Страница 12: ...PERFORMANCE DATA PRESSURE CURVES 5 4 SM FSF045 1 A 0 GB T O B E C O M P L E T E D 5 4 2 Heating...

Страница 13: ...EL CHARACTERISTICS SM FSF045 1 A 0 GB T O B E C O M P L E T E D 6 SOUND LEVEL CHARACTERISTICS 6 1 Sound Pressure Level 6 2 Sound Pressure Level Spectrum Measured as Figure 1 FSF045 FAN SPEED LINE HI M...

Страница 14: ...SOUND LEVEL CHARACTERISTICS SM FSF045 1 A 0 GB T O B E C O M P L E T E D 6 3 Outdoor units 6 4 Sound Pressure Level Spectrum Measured as Figure 2 YFF045 Cooling YFF045 Heating 1m Mic Unit Ground Figur...

Страница 15: ...WIRING DIAGRAMS 7 1 SM FSF045 1 A 0 GB 7 WIRING DIAGRAMS 7 1 Indoor Unit FSF045 7 2 Outdoor Unit YFF045...

Страница 16: ...0 415V 50Hz Fuse A 25 Power Supply Wiring No X Cross Section mm2 5 x 2 5 mm2 Power Supply Wiring No X Cross Section mm2 To IDU 3 x 1 0 mm2 Interconnecting Cable Model No X Cross Section mm2 5x1 0mm2 4...

Страница 17: ...REFRIGERATION DIAGRAMS 9 1 SM FSF045 1 A 0 GB 9 REFRIGERATION DIAGRAMS 9 1 FSF045 YFF045 9 1 1 Cooling Mode 9 1 2 Heating Mode...

Страница 18: ...13 1 Valve Protection Cap end 2 Refrigerant Valve Port use Allen wrench to open close 3 Valve Protection Cap 4 Refrigerant Valve 5 Service Port Cap 6 Flare Nut 7 Unit Back Side 8 Copper Tube When the...

Страница 19: ...n in heating mode Meanwhile compressor and outdoor fan will start running Indoor fan maybe start running after delayed for a period of time to prevent blowing out cold air The RV will be ON after comp...

Страница 20: ...perated again please power off at first and then power off again 2 the low pressure switch can t be short circuited 3 When the protector for low pressure switch has an action compressor and outdoor un...

Страница 21: ...nt Protection After compressor is started up if it s detected that the current is exceeds I0 I0 25A for 3s successively the unit will stop running After compressor has stopped for 3mins the unit will...

Страница 22: ...ption ON OFF Turn ON or OFF unit by pressing this button Mode Select the mode by pressing this button the sequence is Auto cooling dry fan heating AMB Press the AMB button the Save mode room mode offi...

Страница 23: ...rcuit parts without first turning off the power At time such as when the circuit board is to be replaced place the circuit board assembly in a vertical position Normally diagnose troubles according to...

Страница 24: ...s selected Please refer to the performance curve to check the system pressure and other thermodynamic measures 12 2 Simple procedures for checking the Main Parts 12 2 1 Checking Mains Voltage Confirm...

Страница 25: ...EXPLODED VIEWS SPARE PARTS LISTS 13 1 SM FSF045 1 A 0 GB 13 EXPLODED VIEWS SPARE PARTS LISTS 13 1 Indoor Unit FSF045...

Страница 26: ...Electric Box Cover Sub Assy 1 25 30134135 Main Board 1 26 33010037 Capacitor 1 27 42010258 Terminal Board 1 28 43110287 Transformer 1 29 0140484201 Electric Box Assy 1 30 01474027 Protection grill net...

Страница 27: ...EXPLODED VIEWS SPARE PARTS LISTS 13 3 SM FSF045 1 A 0 GB 13 3 Outdoor Unit YFF045...

Страница 28: ...Sensor 20K black 1 19 03005479 Capillary Sub Assy 1 20 03025235 4 way Valve Assy 1 21 07225018 Gas liquid Separator Sub Assy 1 22 39000163 Discharge Temperature Sensor 50K 1 23 03635808 Inhalation Tub...

Страница 29: ...APPENDIX A 14 1 SM FSF045 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL INSTALLATION OPERATION MANUAL FSF045...

Отзывы: