CONTROL SYSTEM

11-2

SM FSF045 1-A.0 GB

11.5 Dry 

Mode

When RT>SPT+2

, the unit will run in cooling mode. Meanwhile, compressor and outdoor fan will 

start running, and indoor fan will run at low fan speed;

When SPT-2

RT

SPT+2

, compressor and outdoor fan will run for 6mins and then stop for 4 mins, 

and they will run like that circularly. Indoor fan will run at low fan speed;

When RT<SPT-2

, compressor and outdoor fan will stop running, while indoor fan will run at low 

fan speed. 

In this mode, the temperature setting range is 16

~30

 and the initial value is 25

11.6 

Refrigerant Recovery mode

• 

Power on the unit, 

• 

Set the A/C at FAN mode, low fan speed by remote controller and the indoor temperature is 
set as 20

• 

Press the light button on remote controller for twice continuously within 5s; The compressor 
will be on to recovery the refrigerant.

After compressor has run for 3mins,  please close the cut-off valve completely.
Notice: 1. After refrigerant is recovered, if the recovery operation should be operated again, please 
power off at first and then power off again.
2. the low pressure switch can’t be short circuited.
3. When the protector for low pressure switch has an action, compressor and outdoor unit will stop 
running automatically. Please close the cut-off valve immediately.

11.7 Turbo 

mode

Press TURBO button in cooling/heating mode, the unit will operate Turbo Mode.
Under this mode, IFAN will operate at super High speed. 
Either pressing TURBO button again or selecting other fan speed can cancel the Turbo Mode.

Turbo Mode does not exist in Auto Mode, Dry Mode and Fan Mode.

11.8 Protections

11.8.1 

Indoor Coil Defrost Protection

IDU freezing protection is functioned by the ICT to prevent the IU exchanger from freezing in cooling 
mode. 

Compressor will stop when ICT <= -2 

for continuous 3 mins.

The unit will not restart until  ICT  

10

 and the compressor is OFF for 6 minutes. 

11.8..2 

High Pressure Protection of Compressor by high pressur switch

When high pressure protection is detected for 3 seconds continuously, the high pressure switch is 
4.2Mpa, the unit will stop and report the fault, it can not resume running automatically and display 
malfunction, it can resume by pressing ON/OFF.

Содержание YFF045

Страница 1: ...YFF Series Indoor Units Outdoor Units FSF045 YFF045 DECEMBER 2010 REFRIGERANT HEAT PUMP R410A SM FSF045 1 A 0 GB...

Страница 2: ...sue for original and changed pages are Original 0 March 2009 Total number of pages in this publication is 53 consisting of the following Page No Revision No Page No Revision No Page No Revision No Tit...

Страница 3: ...ONS 3 1 4 OUTLINE DIMENSIONS 4 1 5 PERFORMANCE DATA PRESSURE CURVES 5 1 6 SOUND LEVEL CHARACTERISTICS 6 1 7 WIRING DIAGRAMS 7 1 8 ELECTRICAL DATA 8 1 9 REFRIGERATION DIAGRAMS 9 1 10 TUBING CONNECTIONS...

Страница 4: ...lure Cold air prevention in heating Self diagnostic Error indications for ease of maintenance LED display Crank heater Optional 1 3 Indoor Unit The indoor unit is floor stanging and can be easily fitt...

Страница 5: ...t Data Sheet Chapter 2 It includes Compressor mounted in a soundproofed compartment Axial fan Outdoor coil with hydrophilic louver fins for RC units Outlet air fan grill Service valves flare type conn...

Страница 6: ...D mm 2080 735 530 9 8 g k t h g i e w d e g a k c a P s t i n u t e l l a p r e p s t i n U s t i n u t h g i e h g n i k c a t S OUTDOOR y r a l l i p a C l o r t n o c t n a r e g i r f e R A 8 3 H...

Страница 7: ...nd EN 14511 Cooling Indoor 27o C DB 19o C WB Outdoor 35 o C DB Heating Indoor 20o C DB Outdoor 7o C DB 6o C WB 3 1 Operating Limits R410A Indoor Outdoor Cooling Upper limit 32o C DB 23o C WB 43o C DB...

Страница 8: ...OUTLINE DIMENSIONS 4 1 SM FSF045 1 A 0 GB 4 OUTLINE DIMENSIONS 4 1 Indoor Unit FSF045 4 2 Outdoor Unit YFF045 Model W H D FSF045 518 1870 395...

Страница 9: ...Data ENTERING AIR WB DB ID Coil o C 15 21 17 24 19 27 21 29 23 32 15 1 TC SC PI 20 1 TC SC PI 25 TC SC PI 30 TC SC PI 35 TC SC PI 40 TC SC PI 46 TC SC PI LEGEND TC Total Cooling Capacity kW SC Sensibl...

Страница 10: ...o C TH Pl TH Pl TH Pl 10 7 2 2 6 10 15 20 LEGEND TH Total Heating Capacity kW PI Power Input kW WB Wet Bulb Temp o C DB Dry Bulb Temp o C ID Indoor OD Outdoor 5 1 3 Capacity Correction Factor Due to T...

Страница 11: ...PERFORMANCE DATA PRESSURE CURVES 5 3 SM FSF045 1 A 0 GB T O B E C O M P L E T E D 5 4 Pressure Curves SAF024 OU7 24 Z R410A 5 4 1 Cooling...

Страница 12: ...PERFORMANCE DATA PRESSURE CURVES 5 4 SM FSF045 1 A 0 GB T O B E C O M P L E T E D 5 4 2 Heating...

Страница 13: ...EL CHARACTERISTICS SM FSF045 1 A 0 GB T O B E C O M P L E T E D 6 SOUND LEVEL CHARACTERISTICS 6 1 Sound Pressure Level 6 2 Sound Pressure Level Spectrum Measured as Figure 1 FSF045 FAN SPEED LINE HI M...

Страница 14: ...SOUND LEVEL CHARACTERISTICS SM FSF045 1 A 0 GB T O B E C O M P L E T E D 6 3 Outdoor units 6 4 Sound Pressure Level Spectrum Measured as Figure 2 YFF045 Cooling YFF045 Heating 1m Mic Unit Ground Figur...

Страница 15: ...WIRING DIAGRAMS 7 1 SM FSF045 1 A 0 GB 7 WIRING DIAGRAMS 7 1 Indoor Unit FSF045 7 2 Outdoor Unit YFF045...

Страница 16: ...0 415V 50Hz Fuse A 25 Power Supply Wiring No X Cross Section mm2 5 x 2 5 mm2 Power Supply Wiring No X Cross Section mm2 To IDU 3 x 1 0 mm2 Interconnecting Cable Model No X Cross Section mm2 5x1 0mm2 4...

Страница 17: ...REFRIGERATION DIAGRAMS 9 1 SM FSF045 1 A 0 GB 9 REFRIGERATION DIAGRAMS 9 1 FSF045 YFF045 9 1 1 Cooling Mode 9 1 2 Heating Mode...

Страница 18: ...13 1 Valve Protection Cap end 2 Refrigerant Valve Port use Allen wrench to open close 3 Valve Protection Cap 4 Refrigerant Valve 5 Service Port Cap 6 Flare Nut 7 Unit Back Side 8 Copper Tube When the...

Страница 19: ...n in heating mode Meanwhile compressor and outdoor fan will start running Indoor fan maybe start running after delayed for a period of time to prevent blowing out cold air The RV will be ON after comp...

Страница 20: ...perated again please power off at first and then power off again 2 the low pressure switch can t be short circuited 3 When the protector for low pressure switch has an action compressor and outdoor un...

Страница 21: ...nt Protection After compressor is started up if it s detected that the current is exceeds I0 I0 25A for 3s successively the unit will stop running After compressor has stopped for 3mins the unit will...

Страница 22: ...ption ON OFF Turn ON or OFF unit by pressing this button Mode Select the mode by pressing this button the sequence is Auto cooling dry fan heating AMB Press the AMB button the Save mode room mode offi...

Страница 23: ...rcuit parts without first turning off the power At time such as when the circuit board is to be replaced place the circuit board assembly in a vertical position Normally diagnose troubles according to...

Страница 24: ...s selected Please refer to the performance curve to check the system pressure and other thermodynamic measures 12 2 Simple procedures for checking the Main Parts 12 2 1 Checking Mains Voltage Confirm...

Страница 25: ...EXPLODED VIEWS SPARE PARTS LISTS 13 1 SM FSF045 1 A 0 GB 13 EXPLODED VIEWS SPARE PARTS LISTS 13 1 Indoor Unit FSF045...

Страница 26: ...Electric Box Cover Sub Assy 1 25 30134135 Main Board 1 26 33010037 Capacitor 1 27 42010258 Terminal Board 1 28 43110287 Transformer 1 29 0140484201 Electric Box Assy 1 30 01474027 Protection grill net...

Страница 27: ...EXPLODED VIEWS SPARE PARTS LISTS 13 3 SM FSF045 1 A 0 GB 13 3 Outdoor Unit YFF045...

Страница 28: ...Sensor 20K black 1 19 03005479 Capillary Sub Assy 1 20 03025235 4 way Valve Assy 1 21 07225018 Gas liquid Separator Sub Assy 1 22 39000163 Discharge Temperature Sensor 50K 1 23 03635808 Inhalation Tub...

Страница 29: ...APPENDIX A 14 1 SM FSF045 1 A 0 GB APPENDIX A INSTALLATION AND OPERATION MANUAL INSTALLATION OPERATION MANUAL FSF045...

Отзывы: