11-24
CONTROL SYSTEM
SM FBFRPM 1-A.0 GB
11.12.2
Condensation Pump.
Mode: Cool, Dry, Auto
Temp:
S
elected desired temper
a
ture
F
a
n: Any
Timer: Any
I FEEL:
Any
Control function:
Prevent Condensed w
a
ter from Overflowing.
ON
OFF
ON
COMP
(WVL)
PUMP
OFF
ON
OPER
LED
OFF
Overflow
W
a
ter Level
Norm
a
l
BLINK
COMP/WVL is
forced OFF
8 min
8 min
Overflow when
unit is ON
Overflow when
unit is OFF
1 min
Notes:
1. The switch used for w
a
ter level detection is closed under norm
a
l condition,
a
nd is open
when w
a
ter overflow.
2
. For the NEC version of MCU, the "Over Flow" & “Norm
a
l” condition
a
re indic
a
ted by
logic “0” & “1”
a
t the LEVEL4 input pin respectively.
3. For the Fujitsu version of MCU, the "Over Flow" & “Norm
a
l” condition
a
re indic
a
ted by
logic “1” & “0”
a
t the LEVEL4 input pin respectively.
4. The “Overflow” condition c
a
n
a
ctiv
a
te the w
a
ter pump in
S
B
a
nd oper
a
ting modes.
Содержание YCF055
Страница 45: ...8 2 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 3 Indoor Units YDF030 8 4 Outdoor Unit GCN 30NRCT...
Страница 46: ...8 3 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 5 Outdoor Unit GCN 37NRC 8 6 Outdoor Unit GCN 37NRCT...
Страница 47: ...8 4 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 7 Outdoor Unit YDF047 8 8 Outdoor Unit YCF055...
Страница 50: ...10 2 REFRIGERATION DIAGRAMS SM FBFRPM 1 A 0 GB 10 1 2 FBF045 FBF060...
Страница 92: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM FBFRPM 1 A 0 GB 14 4 Indoor Unit FBF046 FBF060...
Страница 109: ...15 3 OPTIONAL ACCESSORIES SM FBFRPM 1 A 0 GB 15 3 RCW RCW2 Wiring Connections as Shown on Kit...