CONTROL SYSTEM
Service Manual – YBZ DCI 1-A.1 GB
12-9
12.8.4 Compressor
over Heating Protection
The Discharging temperature is used as the compressor’s internal temperature. If the discharge
temperature rises above a certain level, the operating frequency upper limit is set to keep this
temperature from going up further.
Compressor frequency will be reduced when CTT reaches above 97C
Compressor will stop when CTT reaches 110C
If the unit stops as such protection for 6 times
(the counter will be cleared after the compressor has
run for 7min)
, it can not resume running automatically and display malfunction, it can resume by
power reset.
12.8.5
Compressor over Current Protection
Detect an input current by the CT during the compressor is running, and set the frequency upper
limit from such input current. In case of heat pump model, this control is the upper limit control
function of the frequency which takes priority of the lower limit of four way valve activating
compensation.
Detail
For model 14: Compressor will stop when AC current >= 16.0A for continuously 2.5s
For model 18/30: Compressor will stop when AC current >= 20.0A for continuously 2.5s
If the unit stops as such protection for 6 times (the counter will be cleared after the compressor has
run for 7min), it can not resume running automatically and display malfunction, it can resume by
power reset.
12.8.6
Outdoor Coil Deicing Protection
This protection is for Heat Pump Only
This protection is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than its setting values when finishing the deicing
protection.
In the deicing protection, IFAN is forced OFF.
12.8.6.1 Deicing Starting Conditions
The starting conditions must be made with the outdoor air temperature (OAT) and outdoor coil
temperature (OCT). Under the conditions that the system is in heating operation, after the time for
defrosting is judged to be satisfied, if the temperature for deicing is satisfied after detections for
continuous 1 minute, the deicing operation will start.
Содержание YBZ214
Страница 16: ...OUTLINE DIMENSION 4 2 Service Manual YBZ DCI 1 A 1 GB 4 2 Indoor HZD018 HYD018...
Страница 17: ...OUTLINE DIMENSION Service Manual YBZ DCI 1 A 1 GB 4 3 4 3 Outdoor YBZ214...
Страница 18: ...OUTLINE DIMENSION 4 4 Service Manual YBZ DCI 1 A 1 GB 4 4 Outdoor YBZ318 YBZ430...
Страница 35: ...WIRING DIAGRAM 9 2 Service Manual YBZ DCI 1 A 1 GB 9 3 YAZ214...
Страница 36: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 3 9 4 YAZ318...
Страница 37: ...WIRING DIAGRAM 9 4 Service Manual YBZ DCI 1 A 1 GB 9 5 YAZ430...
Страница 38: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 5 9 6 Wiring connection between IDU and ODU...
Страница 39: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 10 1 10 REFRIGERATION DIAGRAMS...
Страница 40: ...TUBING CONNECTIONS Service Manual YBZ DCI 1 A 1 GB 11 1 11 TUBING CONNECTIONS...
Страница 70: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 9 15 9 Exploded view of outdoor unit YBZ214...
Страница 72: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 11 15 11 Exploded view of outdoor unit YBZ318...
Страница 74: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 13 15 13 Exploded view of outdoor unit YBZ430...
Страница 76: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 15 APPENDIX...