CONTROL SYSTEM
Service Manual – YBZ DCI 1-A.1 GB
12-7
12.5
8 Degree Heat Mode
Under heat mode, press “Save” button, the system will enter into 8 Degree Heat Mode.
1. 8 Degree Heat Mode can not exist together with Sleep mode. If Sleep Mode is selected, 8
degree Heat Mode will be canceled.
2. The SPT will be 8 degree and display will show the SPT,
3.
Under this mode, IFAN can not be changed manually (Including Turbo speed)
4.
Under this mode, IFAN will operate as following table when compressor is ON. When
compressor stops, IFAN will operate as “
Residual heat blowing function” (refer to 12.4.5)
Indoor Fan speed
High
Medium
Low
RAT
<=9
(9,11) >=11
One speed should keep at least 210sec operating before switching to other speeds.
12.6
Auto Cool/Heat Mode
In AUTO mode, the system selects the running mode (COOL/HEAT/FAN) automatically according
to the room temperature. The display shows the actual running mode and setting temperature.
There will be 30s delay for mode conversion.
1. When RAT
≥
26
degree, the cooling mode is selected.
2. When RAT
≤
22 degree, the unit runs in heating mode
3. When 22 degree <RAT<
26
degree, upon initial startup, the unit will enter auto mode and run in
automatic fan mode. If the other mode changes into auto mode, the previous running mode will
remain.
(Except from Dry Mode, system will run in automatic fan mode)
12.7
Dry Mode
Dry Mode is same as Cool Mode in EEV, OFAN and compressor control except following:
1) IFAN will be forced to Low speed.
2) For indoor working under Dry mode, Max capacity output is 90% of Cool Mode
In this mode, the Reverse Valve will be OFF and the temperature setting range is 16~30.
12.8
Protections
There are 4 protection codes.
Normal (Norm) – unit operate normally.
Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased.
HzDown – Compressor frequency is reduced by 1Hz/s (2Hz/s for current protection)
Stop Compressor (SC) – Compressor is stopped.
Содержание YBZ214
Страница 16: ...OUTLINE DIMENSION 4 2 Service Manual YBZ DCI 1 A 1 GB 4 2 Indoor HZD018 HYD018...
Страница 17: ...OUTLINE DIMENSION Service Manual YBZ DCI 1 A 1 GB 4 3 4 3 Outdoor YBZ214...
Страница 18: ...OUTLINE DIMENSION 4 4 Service Manual YBZ DCI 1 A 1 GB 4 4 Outdoor YBZ318 YBZ430...
Страница 35: ...WIRING DIAGRAM 9 2 Service Manual YBZ DCI 1 A 1 GB 9 3 YAZ214...
Страница 36: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 3 9 4 YAZ318...
Страница 37: ...WIRING DIAGRAM 9 4 Service Manual YBZ DCI 1 A 1 GB 9 5 YAZ430...
Страница 38: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 9 5 9 6 Wiring connection between IDU and ODU...
Страница 39: ...WIRING DIAGRAM Service Manual YBZ DCI 1 A 1 GB 10 1 10 REFRIGERATION DIAGRAMS...
Страница 40: ...TUBING CONNECTIONS Service Manual YBZ DCI 1 A 1 GB 11 1 11 TUBING CONNECTIONS...
Страница 70: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 9 15 9 Exploded view of outdoor unit YBZ214...
Страница 72: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 11 15 11 Exploded view of outdoor unit YBZ318...
Страница 74: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 13 15 13 Exploded view of outdoor unit YBZ430...
Страница 76: ...EXPLODED VIEW SPARE PART LIST Service Manual YBZ DCI 1 A 1 GB 15 15 APPENDIX...