9
COOLING PERFORMANCES
Wasted water • Model X 1900 AO
NOMINAL AIR FLOW Qn : 3200 m³/h
X 1100/X 1900
TH 3055
Air temperature at evaporator
inlet (°C)
Waste water supply
BH
BS
Water temperature
°C
10
15
20
15
PT
W
15910 Water consumption
l/h
735
861
1135
PA
W
5205 Water pressure
kPa
18
25
43
21
PS
W
10994
23
12585
25
14176
27
15910
29
15910
31
15910
17
PT
W
16950 Water consumption
l/h
772
905
1193
PA
W
5235 Water pressure
kPa
20
27
47
21
PS
W
10274
23
11969
25
13664
27
15359
29
16950
31
16950
19
PT
W
18000 Water consumption
l/h
811
950
1253
PA
W
5300 Water pressure
kPa
22
30
52
21
PS
W
7800
23
9600
25
11400
27
13200
29
15000
31
16800
21
PT
W
19086 Water consumption
l/h
856
1003
1322
PA
W
5508 Water pressure
kPa
24
33
58
23
PS
W
6881
25
8790
27
10698
29
12607
31
14516
33
16424
23
PT
W
20182 Water consumption
l/h
903
1057
1394
PA
W
5751 Water pressure
kPa
27
37
65
25
PS
W
5807
27
7825
29
9843
31
11861
33
13879
BS =Dry bulb temperature (°C)
BH =Wet bulb temperature (°C)
PT =Total cooling capacity (W)
PA =Power absorbed by the compressor
(W) (without fan motor)
PS =Sensitive cooling capacity (W)
Power absorbed by the indoor fan
= 500 W
Qn =Nominal air flow
Air output correction Qn
0,8xQn 0,9xQn
Qn
1,1xQn 1,2xQn
Total cooling capacity
0,940
0,970
1,000
1,020
1,040
Sensitive cooling capacity
0,890
0,950
1,000
1,050
1,100
Power absorbed
0,970
0,985
1,000
1,005
1,010
Working range
Mini. temperature
Maxi. temperature
Air temperature at evaporator inlet
BH (°C)
15
23
BS (°C)
21
32
Water temperature (°C)
10
34