TROUBLESHOOTING
SM TRIO52 1-A.2 GB
1.3.2 MSMP Fault Code for Indoor Unit:
No
Problem
5 4 3 2 1
Possible
Reason
Corrective
Action
1
RT-1 is disconnected
1. RT-1 is not connected to
controller terminal;
2.RT-1 is cut out;
3.Controller is damaged
In case1, reinstall RT-1 and make sure it’s
connected well; If fault still exists, move to
check case2, use a multimeter to check RT-
1’s resistor, if it’s +
, RT-1 is damaged and
change a new one; if it’s around10K(at 25 ),
then move to case 3; In case 3, change a new
controller.
2
RT-1 is shorted
1. RT-1 is shorted;
2. Controller is shorted
In case 1, use a multimeter to check RT-1’s
resistor, if it’s 0, RT-1 is damaged and change
a new one; if it’s around 10K(at 25 ), then
move to case 2; In case 2, change a new
controller.
3
RT-2 is disconnected
Similar as item 1
Similar as item 1
4
RT-2 is shorted
Similar as item 2
Similar as item 2
5
RGT is disconnected
Similar as item 1
Similar as item 1
6
Reserved
7 Communication
mismatch
Possibly mis-wiring.
8
No Communication
Possibly mis-wiring.
9
No Encoder
Possibly mis-wiring, controller
damaged or fan motor damaged.
10
Reserved
11
Outdoor unit fault
Refer to 1.3.1
12
Reserved
13
Reserved
14
Reserved
15
Reserved
17
Defrost protection
Normal AC protection, no need
action
18
Deicing Protection
Normal AC protection, no need
action
19 Outdoor
Unit
Protection
Refer to 1.3.1
20
Indoor Coil HP
Protection
Normal AC protection, no need
action
21
Overflow Protection
Normal AC protection, no need
action
22
Reserved
23
Reserved
24 EEPROM
Not
Updated
Possibly damaged.
25
Bad EEPROM
Possibly damaged.
26
Bad Communication
ң
ң
Ң
ң
Ң
Check for wiring between IDU and
ODU.
27
Using EEPROM data
ң
ң
Ң
ң
ң
A/C is operating with customized
A/C parameters from EEPROM
Use MEGATOOL to reset to default
parameters
29
No Fault (Heat Mode)
1 1 1 0 1
30
No Fault (Cool, Dry,
Fan Mode)
1 1 1 1 0
31
No Fault (Stand By)
1 1 1 1 1