11-2
CONTROL SYSTEM
SM TRIO52 1-A.2 GB
11.3.2
Target Frequency Setting
The compressor target frequency is a function of the NLOAD number sent from MSMP and
the outdoor air temperature.
Basic Target Frequency Setting
:
NLOAD
Target Frequency
127
Maximum frequency
10 < NLOAD < 127
Interpolated value between minimum and maximum frequency
10
Minimum frequency
0
Compressor is stopped
Target frequency limits as a function of outdoor air temperature (OAT):
OAT Range
Cool mode limits
Heat mode limits
OAT < 6
No limit
6
OAT < 15
MaxFreqAsOAT1H
15
OAT < 24
MaxFreqAsOATC
24
OAT
No limit
MaxFreqAsOAT2H
11.3.3
Frequency Changes Control
Frequency change rate is 1 Hz/sec.
11.3.4
Frequency
Time
Min 10 Minutes
1
Minute
Step 1
Step 3
1
Minute
Step 2
11.3.5
Minimum On and Off Time
3 minutes.