CONTROL SYSTEM
SM YAZ318 1-A.1 GB
11-29
11.10
System Parameters
11.10.1 General
parameters
#
Name
Default
Value
Units
1.
MinOFFTime
3 minute
2.
MinONTime
3 minute
3.
HzUp_CTTOH
2 / 60 /8
Hz / Sec/NA
4.
HzDown1_CTTOH
-2 / 60 /5
Hz / Sec/NA
5.
HzDown2_CTTOH
-4 / 60 /3
Hz / Sec/NA
6.
HzDown1_CCROC
-1 / 2 /1
Hz / Sec/NA
7.
HzUp_ CCROC
1 / 30 /7
Hz / Sec/NA
8.
HzUp_ICTDef
2 /60 / 8
Hz / Sec/NA
9.
HzDown1_ICTDef
-3 / 60 / 4
Hz / Sec/NA
10.
HzDown2_ICTDef
-4 / 30 / 2
Hz / Sec/NA
11.
HzUp_HSTOH
2 / 60 /8
Hz / Sec/NA
12.
HzDown1_HSTOH
-3 / 60 / 4
Hz / Sec/NA
13.
HzDown2_HSTOH
-4 / 30 / 2
Hz / Sec/NA
14.
HzUp_ICTOH
2 /60 / 8
Hz / Sec/NA
15.
HzDown1_ICTOH
-3 / 60 / 4
Hz / Sec/NA
16.
HzDown2_ICTOH
-4 / 30 / 2
Hz / Sec/NA
17.
HzUp_OMTOH
2 /60 / 8
Hz / Sec/NA
18.
HzDown1_OMTOH
-3 / 60 / 4
Hz / Sec/NA
19.
HzDown2_OMTOH
-4 / 30 / 2
Hz / Sec/NA
20.
HzUp_ OVRPWR
1 / 30 /7
Hz / Sec/NA
21.
HzDown1_ OVRPWR
-1 / 2 /1
Hz / Sec/NA
22.
StopRise
0 / 1 / 6
Hz / Sec/NA
23.
DImin
30 minute
24.
DImax
120 Minute
25.
TimeD
1 Minute
26.
DTmin
2 Minute
27.
DIT
10 Minute
28.
CTMRUP
10 Minute
29.
DIF
30 Minute
30.
TCT
240 Second
31.
CompBalanceTimeA
5
minute
32.
IDUChngBalanceTime
2
minute
33.
CompBalanceTimeIA
10 minute
34.
DEICT1
60 second
#
Name
Default
Value
Units
35.
DEICT2
36 second
36.
DEICT3
6 second
37.
DSTF
12
℃
38.
OMTOH0
50
℃
39.
OMTOH1
53
°C
40.
OMTOH2
56
°C
41.
OMTOH3
59
°C
42.
OMTOH4
61
°C
43.
OMTOH5
63
°C
44.
EEVLearning
1
45.
EEVTimeSingleDSH
30 second
46.
EEVTimeSingleCTT
40 second
47.
EEVTimeMultiSHC
30 second
48.
EEVTimeCTTProtection
60 second
49.
EEVTimeSCProtection
30 second
50.
EEVTimeMultiDSHC
30 second
51.
EEVTimeMultiCTT
30 second
52.
EEVTimeMultiSCH
30 second
53.
EEVTimeMultiDSHH
30 second
54.
EEVTimeMultiFBH
30 Second
55.
InstTestIFANHighITime
120 Second
56.
InstTestIFANOffTime
120 Second
57.
InstTestDeltaICT
15
°C
58.
OATInstTst
5
°C
59.
PI_Time_Cnst
50
Sec
60.
EEVLogicType
1
NA
61.
MaxLWTHeating
59
°C
Содержание SX 12 DCI
Страница 17: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 1 4 OUTLINE DIMENSIONS 4 1 Indoor Unit PNXA009 012...
Страница 20: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 4 4 5 Indoor Unit DLF09 12 DCI...
Страница 21: ...OUTLINE DIMENSION SM YAZ318 1 A 1 GB 4 5 4 6 Indoor Unit AWSI HAD007 009 N11 4 7 Indoor Unit AWSI HAD012 N11...
Страница 22: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 6 4 8 Indoor Unit AWSI HFD007 009 N11 4 9 Indoor Unit AWSI HFD012 N11...
Страница 23: ...OUTLINE DIMENSION SM YAZ318 1 A 1 GB 4 7 4 10 OUTDOOR UNIT YAZ318...
Страница 34: ...OPERATING CURVES SM YAZ318 1 A 1 GB 6 1 6 OPERATING CURVES 6 1 Model YAZ3 018 DCI 6 1 1 Cooling Technician Mode...
Страница 35: ...OPERATING CURVES 6 2 SM YAZ318 1 A 1 GB 6 1 2 Heating Technician Mode...
Страница 36: ...OPERATING CURVES SM YAZ318 1 A 1 GB 6 3 6 1 3 Tubing Length correction Factor...
Страница 41: ...TUBING CONNECTIONS SM YAZ318 1 A 1 GB 10 1 10 TUBING CONNECTIONS...
Страница 86: ...EXPLODED VIEW AND SPARE PART LIST SM YAZ318 1 A 1 GB 14 1 14 APPENDIX A INSTALLATION AND OPERATION MANUAL...