CONTROL
SYSTEM
11-6
SM YAZ318 1-A.1 GB
11.4
Indoor Unit Control
11.4.1
Indoor Fan Control
10 Indoor fan speeds are determined for each model. 5 speeds for each mode cool/dry/fan
or heat.
When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate
constantly at set speed.
When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual
speed is set according to the cool/heat load.
Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan
speed is selected and under the following conditions:
Difference between set point and actual room temperature is higher than 3 degrees.
Room temperature is higher than 22
°
C for cooling or less than 25
°
C for heating.
11.4.2 Cool
Mode
NLOAD is calculated according to the difference between actual room temperature and user
set point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In Auto Fan user setting, fan speed will be adjusted automatically according to the
calculated NLOAD.
11.4.3 Heat
Mode
NLOAD is calculated according to the difference between actual room temperature and user
set point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In Auto Fan user setting, fan speed will be adjusted automatically according to the
calculated NLOAD.
11.4.3.1
Temperature Compensation
In wall mounted, ducted, and cassette models, 3 degrees are reduced from room
temperature reading (except when in I-Feel mode), to compensate for temperature
difference between high and low areas in the heated room, and for coil heat radiation on
room thermistor.
The temperature compensation can be enabled/disabled by shortening of J2 on the indoor
unit controller.
Model
J2 Shorted
J2 Opened
Wall mounted
Compensation Disabled
Compensation Enabled
Cassette
Compensation Enabled
Compensation Disabled
Ducted
Compensation Enabled
Compensation Disabled
Floor/Ceiling
Compensation Disabled
Compensation Enabled
Содержание SX 12 DCI
Страница 17: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 1 4 OUTLINE DIMENSIONS 4 1 Indoor Unit PNXA009 012...
Страница 20: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 4 4 5 Indoor Unit DLF09 12 DCI...
Страница 21: ...OUTLINE DIMENSION SM YAZ318 1 A 1 GB 4 5 4 6 Indoor Unit AWSI HAD007 009 N11 4 7 Indoor Unit AWSI HAD012 N11...
Страница 22: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 6 4 8 Indoor Unit AWSI HFD007 009 N11 4 9 Indoor Unit AWSI HFD012 N11...
Страница 23: ...OUTLINE DIMENSION SM YAZ318 1 A 1 GB 4 7 4 10 OUTDOOR UNIT YAZ318...
Страница 34: ...OPERATING CURVES SM YAZ318 1 A 1 GB 6 1 6 OPERATING CURVES 6 1 Model YAZ3 018 DCI 6 1 1 Cooling Technician Mode...
Страница 35: ...OPERATING CURVES 6 2 SM YAZ318 1 A 1 GB 6 1 2 Heating Technician Mode...
Страница 36: ...OPERATING CURVES SM YAZ318 1 A 1 GB 6 3 6 1 3 Tubing Length correction Factor...
Страница 41: ...TUBING CONNECTIONS SM YAZ318 1 A 1 GB 10 1 10 TUBING CONNECTIONS...
Страница 86: ...EXPLODED VIEW AND SPARE PART LIST SM YAZ318 1 A 1 GB 14 1 14 APPENDIX A INSTALLATION AND OPERATION MANUAL...