CONTROL
SYSTEM
11-4
SM YAZ318 1-A.1 GB
11.3.1.1.3 Model Plug & Indoor Capacity Test
This test is performed for both single split channel and multi split channel:
Test
How to check?
Error to report?
System Action
(ODU Mode)
Jumper is inserted/DIP
is configured
ODU model is 0 (
zero
).
"Missing ODU configuration"
Force to Idle
mode.
Jumper/DIP is not
defined in the software
ODU model is not Q.
"Undefined ODU model"
Force to Idle
mode
IDU-ODU capacity
group mismatch
When ODU model is Q, and
the capacity group is not
allowed.
"
Mismatch between IDU and
ODU models "
Except for ITU
mode,
Force to
Idle mode
The following combinations show the allowed and not allowed capacity group:
Is it allowed capacity group?
Indoor Capacity
ODU Model
Communication channel
0 1 2 3 4
Single- Non Hydro
No
No
No
Yes No
Single- Hydro
No No No No No
Com Channel 1
Yes
Yes No No No
Com Channel 2
Yes
Yes No No No
Com
Channel
3
No No No No No
S
(YBD022/YAZ318)
Com Channel 4
Yes
Yes No No No
Notes
1. The outdoor will keep establishing normal communication with the indoor or DMSMP.
2. The outdoor will show diagnostics normally.
3. The SB LED will keep ON as long as the power is on.
4. Once the unit is forced to Idle due to either of the above, it will keep checking the
above items, until the system is recovered.
11.3.2 Communication
with Indoor Units
11.3.2.1
Communication Failures Definition
Two types of communication failures are diagnosed. The communication failures are
checked separately for each IDU channel.
11.3.2.2
‘Bad Communication’ fault
The system keeps a balance of a good/bad communication packet ratio for each active
communication channel. When the ratio getting high , system enters ‘Bad Communication’
fault.
11.3.2.3
‘No Communication’ fault
If no legal transmission or no message received for 30 seconds, system enters ‘No
Communication’ fault.
When in ‘No Communication’ fault, the system will act as following:
•
If there is no communication in all channels, the following will be performed:
1. The unit changes to SB.
2. The system will scan all the communication.
Содержание SX 12 DCI
Страница 17: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 1 4 OUTLINE DIMENSIONS 4 1 Indoor Unit PNXA009 012...
Страница 20: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 4 4 5 Indoor Unit DLF09 12 DCI...
Страница 21: ...OUTLINE DIMENSION SM YAZ318 1 A 1 GB 4 5 4 6 Indoor Unit AWSI HAD007 009 N11 4 7 Indoor Unit AWSI HAD012 N11...
Страница 22: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 6 4 8 Indoor Unit AWSI HFD007 009 N11 4 9 Indoor Unit AWSI HFD012 N11...
Страница 23: ...OUTLINE DIMENSION SM YAZ318 1 A 1 GB 4 7 4 10 OUTDOOR UNIT YAZ318...
Страница 34: ...OPERATING CURVES SM YAZ318 1 A 1 GB 6 1 6 OPERATING CURVES 6 1 Model YAZ3 018 DCI 6 1 1 Cooling Technician Mode...
Страница 35: ...OPERATING CURVES 6 2 SM YAZ318 1 A 1 GB 6 1 2 Heating Technician Mode...
Страница 36: ...OPERATING CURVES SM YAZ318 1 A 1 GB 6 3 6 1 3 Tubing Length correction Factor...
Страница 41: ...TUBING CONNECTIONS SM YAZ318 1 A 1 GB 10 1 10 TUBING CONNECTIONS...
Страница 86: ...EXPLODED VIEW AND SPARE PART LIST SM YAZ318 1 A 1 GB 14 1 14 APPENDIX A INSTALLATION AND OPERATION MANUAL...