How to take out front grille

Please follow the steps below to take out front grille if necessary  during servicing.

1.Set the vertical airflow direction louver to the horizontal position.

2.Slide down the two caps of PNV 007/009/012 on the front grille as shown in 

the illustration at right, then remove  the two mounting screws. (If the unit is 

PNV015/018/021, it has three caps).

3.Pull the lower section of the front grille towards your to remove the front grille.

Check the drainage

1  Open front panel and remove air filters.

 (Drainage checking can be carried out without removing the front grill).

2  Pour a glass of water into the drain tray-styrofoam.

3  Ensure that water flows out from drain hose of the indoor unit.

Height Compensation Setting 

The Compensation setting according to installation height can be done by using the dip switch 11 and 12 on controller PCB.

Installation Height

Height Code

DS11

DS12

2.3-2.7(m)

H0

OFF

OFF

2.7-3.1(m)

H1

OFF

ON

3.1-3.5(m)

H2

ON

OFF

>3.5(m)

H3

ON

ON

     

Note

     

1.Please disconnect the unit from power supply when change these settings.

 

    2.If you feel too noisy, please set DS11 and DS12 to lower height code level.

Vertical airflow 

deflection louver

(Move the vertical 

vane to horizontal)

Drain traystyrofoam

4

ELECTRICAL WRING CONNECTION

Terminal block (4P)

Power supply 

Terminal block (2P)

Power supply wiring

Tie the communication wiring with clamp tightening

Fix the power supply wiring under the clip tightening

Connect the drainage pipe

1  Use standard hard PVC pipe (19mm) for the drain pipe.

   2  Use the drain hose to change the direction.

   3  Insert the drain hose until it connects the drain port very well, and then secure it tightly with the hose clamp. 

   4  After checking the drainage, wrap the drain hose with the insulation and clamps.