12-6
CONTROL SYSTEM
SM FLODCI 2-A.4 GB
12.3 Cool
Mode
NLOAD is calculated according to the difference between actual room temperature and user set
point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
NLOAD.
12.4 Heat
Mode
NLOAD is calculated according to the difference between actual room temperature and user set
point temperature by PI control.
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the calculated
NLOAD.
12.4.1 Temperature
Compensation
In wall mounted, ducted, and cassette models, 3 degrees are reduced from room temperature
reading (except when in I-Feel mode), to compensate for temperature difference between high and
low areas in the heated room, and for coil heat radiation on room thermistor.
The temperature compensation can be enabled/disabled by shortening of J2 on the indoor unit
Controller
Model
J2 Shorted
J2 Opened
Wall mounted
Compensation Disabled
Compensation Enabled
Cassette
Compensation Enabled
Compensation Disabled
Ducted
Compensation Enabled
Compensation Disabled
Floor/Ceiling
Compensation Disabled
Compensation Enabled
12.4.2
Indoor Fan Control in Heating Mode
Indoor fan speed depends on the indoor coil temperature:
12.5
Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according
to the difference between actual room temperature and user set point temperature (.T). Unit will
switch from cool to heat when compressor is off for 3 minutes, and .T < -3.
Unit will switch from heat to cool when compressor is off for 5 minutes, and .T < -3.
CONTENTS
Содержание FLO 18 DCI
Страница 15: ...4 2 OUTLINE DIMENSIONS SM FLODCI 2 A 4 GB 4 3 Outdoor Unit GC 21 4 4 Indoor Unit FLO 30 CONTENTS...
Страница 16: ...4 3 OUTLINE DIMENSIONS SM FLODCI 2 A 4 GB 4 5 Outdoor Unit GC 24 24 Z 30 CONTENTS...
Страница 43: ...8 2 WIRING DIAGRAMS SM FLODCI 2 A 4 GB 8 3 Indoor Outdoor Units FLO 24 DCI OUTDOOR UNIT INDOOR UNIT CONTENTS...
Страница 93: ...14 3 EXPLODED VIEWS AND SPARE PARTS LISTS SM FLODCI 2 A 4 GB 14 3 Outdoor Unit GC 18 DCI CONTENTS...
Страница 95: ...14 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM FLODCI 2 A 4 GB 14 5 Outdoor Unit GC 21 CONTENTS...
Страница 97: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS SM FLODCI 2 A 4 GB 14 7 Indoor Unit FLO 24 DCI CONTENTS...
Страница 99: ...14 9 EXPLODED VIEWS AND SPARE PARTS LISTS SM FLODCI 2 A 4 GB 14 9 Indoor Unit FLO 30 DCI CONTENTS...
Страница 101: ...14 11 EXPLODED VIEWS AND SPARE PARTS LISTS SM FLODCI 2 A 4 GB 14 11 Outdoor Unit GC 24 GC 30 CONTENTS...
Страница 103: ...14 13 EXPLODED VIEWS AND SPARE PARTS LISTS SM FLODCI 2 A 4 GB 14 13 Outdoor Unit GC 24 Z CONTENTS...