12-4
CONTROL SYSTEM
SM GCD030 1-A.0 GB
Correction by OAT (EEVOATCrct):
ODU Mode
OAT
EEVOATCrct
Single Split
Multi Split
Cool
> 35
3*(OAT-35)
5*(OAT-35)
<=35
1*(OAT-35) 2*(OAT-35)
Faulty
0
0
Heat
>7
3*(OAT-7) 3*(OAT-7)
<=7
2*(OAT-7) 2*(OAT-7)
Faulty
0
0
Correction by actual compressor frequency:
ODU Mode
EEVFreqCrct (Single)
EEVFreqCrct (multi)
Cool
-1*(
MaxFreqC
-Actual Frequency)
0*(
MaxFreqC
-Actual Frequency)
Heat
-1*(
MaxFreqH
-Actual Frequency)
0*(
MaxFreqH
-Actual Frequency)
The following table describes the time calculations for the Open loop and the Correction value:
During
BalanceTime
minutes after
compressor starts up
After
BalanceTime
minutes
EEV Open Loop
Yes, continuously (always)
Yes, continuously (always)
EEV
CV
Single
No (set to 0)
Yes, every EEVTime
seconds from the last calculation point.
Multi
Yes, every EEVTime
seconds from the last calculation point,
OR whenever the number of active IDUs is changed
For EEVTime parameter refer to the relevant each section described below.
CONTENTS
Содержание CKD 30 DCI
Страница 38: ...7 2 SOUND LEVEL CHARACTERISTICS SM GCD030 1 A 0 GB SX 30 CKD 30 FAN SPEED LINE HI ME LO CONTENTS ...
Страница 41: ...9 1 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 WIRING DIAGRAMS 9 1 Indoor Unit PNX 30 DCI INDOOR UNIT CONTENTS ...
Страница 42: ...9 2 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 2 Indoor Unit SX 30 DCI CONTENTS ...
Страница 43: ...9 3 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 3 Indoor Unit CKD 30 DCI 9 4 Indoor Unit DLS 30 DCI CONTENTS ...
Страница 82: ...14 3 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 3 Indoor Unit PNX 30 DCI CONTENTS ...
Страница 84: ...14 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 5 Indoor Unit SX 30 DCI CONTENTS ...
Страница 89: ...14 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 10 Outdoor Unit GCD 030 CONTENTS ...