12-2
CONTROL SYSTEM
SM GCD030 1-A.0 GB
LoadDeadZone
Seting:
Communication Channel
Model P (DCI80)
Cooling
Heating
Single Spit Channel
127
127
Multi Split Channel
90
127
12.1.4
Frequency Changes Control
When the unit is running normally , the compressor frequency change rate is 1 Hz/sec.
12.1.5
Compressor Starting Control
12.1.5.1
Compressor starting control for
GCD 030
When started, compressor frequency must reach 30 Hz, and not go down below 30 Hz during the
first 5 minutes of compressor operation, except when compressor should be stopped (see next
sections for explanation).
When Reaching
Step1Freq
Hz and
Step2Freq
Hz (for the first time during one continuous compressor
operation) during compressor acceleration, compressor acceleration will be stopped for one minute
and then continue.
Note
: If compressor is working constantly at a frequency between the step frequency and step
frequency – 10 Hz, then it will remain in its current frequency until one minute is over. After that
minute is over, there is no need to stop compressor acceleration again at the step frequency.
When compressor frequency is equal or higher than
Step2Freq
Hz, further increasing of compressor
frequency will be done in steps of
HzDown1
Hz every one minute.
The Normal acceleration/deceleration rate will be kept during these steps.
Decelartion does not require steps.
The steps limitation is ignored during Deicing protection.
This logic should be followed every time frequency should be increased over
Step2Freq
, and not
only once.
Compressor frequency can not go over
Step3Freq
Hz during the first 10 minutes of continues
compressor operation (excluding Deicing).
12.1.6
Minimum On and Off Time
3 minutes
12.1.7
Indoor Fan Control
8 Indoor fan speeds are determined for each model. 4 speeds for cool/dry/fan modes and 4 speeds
for heat mode.
When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly
at set speed.
When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set
according to the cool/heat load.
12.1.7.1 Turbo
Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is
selected and under the following conditions:
Difference between set point and actual room temperature is bigger then 3 degrees.
Room temperature > 22 for cooling, or < 25 for heating.
1
2.1.8
Outdoor Fan Control
12.1.8.1
Outdoor Fan Control for DCI 80 Z
OFAN operates between
OFMinRPM
to
OFMaxRPM
.
The OFAN will be off when the compressor is off.
when compressor is OFF, and HST>55 or faulty, OFAN will remain ON in 500 rpm for up to three
minutes.
IF HST falls below 55, OFAN will be switched off immediately.
CONTENTS
Содержание CKD 30 DCI
Страница 38: ...7 2 SOUND LEVEL CHARACTERISTICS SM GCD030 1 A 0 GB SX 30 CKD 30 FAN SPEED LINE HI ME LO CONTENTS ...
Страница 41: ...9 1 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 WIRING DIAGRAMS 9 1 Indoor Unit PNX 30 DCI INDOOR UNIT CONTENTS ...
Страница 42: ...9 2 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 2 Indoor Unit SX 30 DCI CONTENTS ...
Страница 43: ...9 3 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 3 Indoor Unit CKD 30 DCI 9 4 Indoor Unit DLS 30 DCI CONTENTS ...
Страница 82: ...14 3 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 3 Indoor Unit PNX 30 DCI CONTENTS ...
Страница 84: ...14 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 5 Indoor Unit SX 30 DCI CONTENTS ...
Страница 89: ...14 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 10 Outdoor Unit GCD 030 CONTENTS ...